Chapter 10 Protective Function
10-4
Cx2000 AC Drive
F59: Stall prevention can be set as the table below.
F59
Stall prevention
Set Value
During
Deceleration
During
constant
speed
During Accele
ration
BIT 2
BIT 1
BIT 0
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7
For example, set F59 to 3 to make stall prevention active during Acceleration
and constant run.
When stall prevention is executed during acceleration or deceleration, Accel/Decel
time may take longer than the user-setting time.
When stall prevention is activated during constant run, t1, t2 executed in
accordance with the value set in ACC - [Accel time] and dEC - [Decel time].
During acceleration
During constant run
F60
t1
t2
Relay output
DC voltage
Output Freq.
During deceleration
Relay output
Output current
Output frequency