![Larsen & Toubro C*2000 Series Скачать руководство пользователя страница 175](http://html1.mh-extra.com/html/larsen-and-toubro/c-2000-series/c-2000-series_user-manual_676507175.webp)
Chapter 13 Product specifications and options
13-4
Cx2000 AC Drive
Protective function
Faults
Over voltage, low voltage, over current, short circuit, ground current detection,
inverter overheat, motor overheat, input and output phase loss, overload protection,
communication error, loss of frequency command, hardware fault, cool fan trip, brake
error.
Alarm
Stall prevention, overload
Momentary
Power Loss
1)
Below 16 msec: Continuous operation
Above 16 msec: Auto restarting.
Note 1): the rated input voltage is 220V for 230V class, 440V for 415V class, and the rated
input is subject to HD.
Structure and application environment
Protection degree
Opening (IP00), IP40 (Ambient Temperature 40
◦
C)
2)
Application
temperature
HD operation: - 10 ~ 50
℃
(no freezing)
ND operation: - 10 ~ 40
℃
(no freezing)
Storage temperature
-20 C ~ 65 C
Application humidity
Below relative humidity 90% RH (
no condensation)
Altitude/Vibration
Below 1000m, 5.9/sec
2
(0.6G)
Atmospheric pressure
70~106 kPa
Installation environment There shall not be corrosive air,
combustible gas, oil mist, dust and so on.
Note 2) under development
13.2
Rated current of inverter decreasing
13.2.1 Influence of carrier frequency on rated current decreasing
Influence of carrier frequency on rated current decreasing
0 1
2
3
4
5
6
7
8
9
10 11 12 13 14 15
50.0
60.0
70.0
80.0
90.0
100.0
110.0
Carrier /K Hz
系
Influence of carrier frequency on rated current decreasing
Carrier /K Hz
0
1
2
3
4
5
84.0
86.0
88.0
90.0
92.0
94.0
96.0
98.0
100.0
102.0
系
Figure 13-1 operating as CT Figure 13-2 operating as VT
Caution
1) The above graph is only applied when the inverter is operated in the allowable temperature. Pay
attention to the air cooling when the inverter is installed in a panel box, and the inside temperature
should be within an allowable temperature range.
2) The output current value on the above graph is the proportion of inverter’s rated current; it is
applied to relative rated motor of the inverter.