Chapter 5 – Function list
5-20
Cx2000 AC Drive
LED
display
Address
for
comm
Parameter
name
Range
Description
Factory
defaults
Adj.
During
run
Page
H73
1349
Monitoring
item select
0
~
2
One of the following can be monitored via
vOL(User display select).
0
O
9-2
0
Output voltage [V]
1
Output power [kW]
2
Torque [kgf m]
H74
134A
Gain for
Motor rpm
display
1
~
1000[%]
This parameter is used to change the motor
rotating speed (r/min) to mechanical speed
(m/mi) and display it.
100
O
9-1
H75
134B
DB resistor
operating
rate limit
select
0
~
1
0
Unlimited
1
O
10-8
1
Use DB resistor for the rate set in H76.
H76
134C
DB resistor
operating
rate
0
~
30
[%]
Set the percent of DB resistor operating rate
to be activated during one sequence of
operation.
10
O
H77
1)
134D
Cooling
fan control
0
~
1
0
Cooling fan is always on
0
O
8-29
1
Keeps ON when its temp is higher than
inverter protection limit temp.
Activated only during operation when its
temp is below that of inverter protection
limit.
H78
134E
Operating
method
select when
cooling fan
malfunctions
0
~
1
0
Continuous operation when cooling fan
malfunctions.
1
O
8-29
1
Operation stopped when cooling fan
malfunctions.
H79
134F
S/W
version
X.X
This parameter displays the inverter software
version.
X.X
X
1)
: Single phase 0.1/0.2kW, three phase 200V 0.1/0.2/0.4KW and three phase 400V 0.4KW are NO FAN
TYPE, so this parameter has no displaying.
Function group 2