Chapter 4 Parameter setting
4-15
Cx2000 AC Drive
Frequency setting via Terminal AIN (V1) and Driving via Pressing Run Key
1
-. Apply power to the inverter.
2
-. 0.00 is displayed on the inverter keypad.
-. Press the Up (
) key three times.
3
-. drv. is displayed and the drive pattern is selectable.
-. Press the ENT key.
4
-. Present setting value is 1 (operation of inverter terminal).
-. Press the Down (
) key once.
5
-. Press the ENT key after 0 is displayed.
-. Press the ENT key again when 0 is blinking.
6
-. drv is displayed, drive pattern is set via the Run key on the keypad.
-. Press the Up (
) key once.
7
-. Freq. is displayed. Frequency setting method is selectable.
-. Press the ENT key.
8
-. Present frequency setting is 0 (frequency setting via keypad).
-. Press the Up (
) key three times.
9
-. Press the ENT key after 3 is displayed [Terminal AIN (V1)].
-. Press the ENT key over again when 3 is blinking.
10
-. Freq. is displayed; frequency setting method is made via Terminal AIN (V1).
-. Press the Down (
) key four times to move the frequency display status.
-. V1 voltage is adjusted so that output frequency is 10.00 Hz.
11
-. Press Run key on the inverter keypad.
-. Run lamp on the inverter keypad starts to blink with FWD lamp lit and accelerating
frequency displayed on the keypad.
-. When frequency reaches 10 Hz, press (STOP/RST) key of inverter keypad once.
12
-. RUN (operating) lamp on the inverter keypad blinks over again, with decelerating
frequency displayed on the keypad.
-. When fun frequency reaches 0Hz, RUN and FWD lamps are blacked out and 10.00 is
displayed on the keypad.
Connection diagram
Run curve