Chapter 8 Application
8-31
Cx2000 AC Drive
Press Enter (●) key after setting in H93. H93 will be displayed again after initialization is complete.
Password register
Group
Code
Item
Set
Value
Setting
Range
Initial
Unit
Function group 2
H94
Password register
-
0 ~ FFFF
0
H95
Parameter lock
-
0 ~ FFFF
0
Register password for Parameter lock (H95).
Password should be Hex decimal. (0 ~ 9, A, B, C, D, E, F)
Caution
After setting modification lock function of H95, Do not forget the registered password. If you try to
release lock, you need the registered password.
Factory default password is 0. Enter the new password except 0.
Follow the steps below when you register the password for the first time.
No
Note
Keypad display
1
Move to H94 code
H94
2
Press Enter (
) key twice.
0
3
Register password. (Ex: 123)
123
4
123 will blink when Enter (
) key is pressed.
123
5
Press Enter (
) key.
H94
Follow the table below to change the password. (Current PW: 123 -> New PW: 456)
No
Note
Keypad display
1
Move to H94 code.
H94
2
Press Enter (
) key.
0
3
Enter any number (e.g.: 122).
122
4
Press the Enter (
) key. 0 is displayed because
wrong value was entered. Password cannot be
changed in this status.
0
5
Enter the right password.
123
6
Press Enter (
) key.
123
7
Enter the new password.
456
8
Press the Enter (
) key. Then “456” will blink.
456
9
Press Enter (
) key.
H94