Chapter 7 Basic Functions
7-12
Cx2000 AC Drive
7.4 Accel/Decel time and pattern setting
Accel/Decel time setting based on Max frequency
Group
Code Item
Set value Range
Initial Unit
Drive group
ACC
Accel time
-
0.0 ~ 6000.0
20.0
Sec
dEC
Decel time
-
0.0 ~ 6000.0
20.0
Sec
Function group1
F21
Max Frequency
-
40.00~ 400.00 50.00
Hz
Function group2
H70
Frequency reference for
Accel/Decel
0
0 ~ 1
0
H71
Accel/Decel time scale
-
0 ~ 2
1
Set the desired Accel/Decel time at ACC/dEC in Drive group.
If H70 in function group 2 is set to 0 (Max frequency), Accel/Decel time is the time that takes to reach
the max freq from 0 Hz, it does not relate with the operation frequency.
Desired Accel/Decel time unit is settable at the H71.
Frequency reference for Accel/Decel (H70)is set to 0 (Max frequency), if Max frequency(F21) is set to 60Hz,
Accel/Decel time 5 sec, when run frequency is set to 30Hz, time to reach 30Hz would be 2.5 sec.
Corresponding to load property, when more precious Accel/Decel time is desired, the setting unit can be
changed as follows.
In LTVF-Cx2000, number display is available up to 5. Therefore, if time unit is set to 0.01 sec, Max
Accel/Decel time would be 600.00 sec., with changes as follows:
Code Item
Set value Setting range for
Accel/Decel time
Setting content
H71
Setting unit for
Accel/Decel time
0
0.01~600.00
Unit: 0.01sec
1
0.1~6000.0
Unit: 0. 1sec
2
1~60000
Unit: 1sec
R un com m and
R un F req .
30H Z
A ccel tim e
D ecel tim e
M ax.freq.
60H Z