Chapter 5 – Function list
5-18
Cx2000 AC Drive
Function group 2
LED
display
Address
for
comm
Parameter name Range
Description
Factory
defaults
Adj.
During
run
Page
H55
1)
1337
PID output
frequency
high limit]
0.10
~
400.00
[Hz]
This parameter limits the amount of the
output frequency through the PID control.
The value is settable within the range of
Max frequency (F21) and Start frequency
(F23).
60.00
O
8-10
H56
1338
PID output
frequency
low limit
0.10
~
400.00
[Hz]
0.50
O
H57
1339
PID
standard
value select
0
~
4
Selects PID standard value.
Standard value is indicated in “rEF” of
Drive group.
0
X
8-10
0
Loader digital setting 1
1
Loader digital setting 2
2
V1 terminal setting : 0~10V
3
I terminal setting: 0~20mA
4
Setting as a RS-485 communication
H58
133A
PID control
unit select
0
~
1
Selects a unit of the standard value or
feedback amount.
0
X
0
Frequency [Hz]
1
Percentage [%]
H61
133D
Sleep delay time
0.0
~
2000.0
[sec]
Sets a sleep delay time in PID drive.
60.0
X
8-10
H62
133E
Sleep frequency
0.00
~
400.00
[Hz]
Sets a sleep frequency when executing a
sleep function in PID control drive.
You can‟t set more than Max. frequency
(F21)
0.00
O
H63
133F
Wake up level
0.0
~
100.0[%]
Sets a wake up level in PID control drive.
35.0
O
H64
1340
KEB drive select 0
~
1 Sets KEB drive.
0
X
8-27
H65
2)
1341
KEB action
start level
110.0
~
140.0[%]
Sets KEB action start level according to
level.
125.0
X
1)
: Set H49 to 1 (PID control) to display this parameter.
2)
:
It is indicated when setting H64 to 1.# KEB does not operate when cut power after loading ting input (about
10% ).
Function group 2