Safety Instructions
iv
Cx2000 AC Drive
(3) Trial run
Check all parameters during operations. Changing parameter values might be required depending
on the load.
Always apply permissible range of voltage to each terminal as indicated in this manual. Otherwise,
it could lead to inverter damage.
(4) Operation methods
When the Auto restart function is selected, stay away from the equipment as a motor will restart s
uddenly after an alarm stop.
The Stop key on the keypad is valid only when the appropriate function setting has been
made. Prepare an emergency Stop switch separately.
If an alarm reset is made with the reference signal present, a sudden start will occur. Check that
the reference signal is turned off in advance. Otherwise an accident could occur.
Do not modify or alter anything inside the inverter.
Motor might not be protected by electronic thermal function of inverter.
Do not use a magnetic contactor on the inverter input for frequent starting/stopping of the inverter.
Use a noise filter to reduce the effect of electromagnetic interference. Otherwise nearby electronic
equipment may be affected.
In case of input voltage unbalance, install AC reactor. Power Factor capacitors and generators
may become overheated and damaged due to potential high frequency noise transmitted from
inverter.
Parameters will be set to default settings after parameter initializing. Do re-set necessary
parameters before starting the inverter.
Inverter can easily be set to high-speed operations, Verify capability of motor or machinery prior to
operating unit.
Stopping torque is not produced when using the DC-Break function. Install separate equipment
when stopping torque is needed.
(5) Fault prevention precautions
Provide a safety backup such as an emergency brake which will prevent the machine and
equipment from hazardous conditions if the inverter fails
(6) Maintenance, inspection and parts replacement
Do not conduct a megger (insulation resistance) test on the control circuit of the inverter.
Refer to Chapter 12 for periodic inspection (parts replacement)