Chapter 10 Protective Functions
10-1
Cx2000 AC Drive
10. Protective Functions
10.1Electronic Thermal
Group
Code Parameter
Set Value Range
Initial
Unit
Function
group 1
F50
ETH (Electronic thermal)
select
1
0 ~ 1
0
F51
Electronic thermal level
for 1 minute
-
50 ~ 200 150
%
F52
Electronic thermal level
for continuous
-
50 ~ 150 100
%
F53
Motor cooling type
-
0 ~ 1
0
Select F50 – [Electronic thermal select] to 1.
It activates when the motor is overheated (time-inverse). If current is greater
than that set in F51, inverter output is turned off for the preset time in F51.
F51: Enter the value of max current that is capable of flowing to the motor
continuously for one minute. It is set in percent of motor rated current. The
value cannot be set lower than F52.
F52: Enter the amount of current for continuous operation. Normally motor rated
current is used. It cannot be set greater than F51.
F53: For a standard motor, cooling fans are equipped; however, cooling effects
can be achieved when a motor is running at low speed. A separately powered
cooling fan is used.
F53
Motor cooling type
0
Standard motors having a cooling fan directly
connected to the shaft
1
Special motor that uses a separately powered
cooling fan.
100
95
65
20
60
H53 = 1
H53 = 0
Current for continuous operation [%]
Output freq [Hz]