Chapter 8 Application
8-10
Cx2000 AC Drive
8.7 PID control
Group
Code Item
Set Value Setting Range
Initial
Unit
Function
group 2
H49
PID Operation selection
1
0 ~ 1
0
-
H50
PID Feedback selection
-
0 ~ 2
0
-
H51
P gain for PID controller
-
0.0~ 999.9
300.0
%
H52
Integral time for PID controller
(I gain)
-
0.1~ 32.0
1.0
sec
H53
Differential time for PID
controller (D gain)
-
0.0~30.0
0
sec
H54
PID mode select
-
0 ~ 1
0
-
H55
PID output frequency high limit
-
0.1 ~ 400.0
60.0
Hz
H56
PID output frequency low limit
-
0.10 ~ 400.00 0.50
Hz
H57
PID reference select
-
0 ~ 4
0
-
H58
PID unit select
-
0 ~ 1
0
-
H61
Sleep delay time
-
0.0~2000.0
60.0
sec
H62
Sleep frequency
-
0.00 ~ 400.00 0.00
Hz
H63
Wake-up level
-
0.0 ~ 100.0
35.0
%
I/O group
I17
Multi-function input terminal
selection
21
0 ~ 27
-
-
Drive
group
rEF
PID reference
-
0.00 ~ 400.00
/ 0.0 ~ 100.0
0.00
/ 0.0
Hz
/ %
FbK
PID feedback
-
0.00~ 400.00
/ 0.0 ~ 100.0
0.00
/ 0.0
Hz
/ %
In order to control the amount of following water, pressure and temperature, do PID control to
inverter output frequency.
Select H49 of function group 2 as a 1 (PID drive select). Then REF and FBK category show.
Set PID reference value in REF and real PID feedback amount is monitored at the FBK
PID drive is classified as two which are Normal PID mode and Process PID mode. It can be set
in the H54 (PID mode select)
H50: Select the feedback type of PID controller.
H50
PID Feedback
select
0
Terminal I input (0 ~ 20[mA] )
1
Terminal AI(V input) (0 ~ 10[V])
2
Communication RS-485