Chapter 5 – Parameter list
5-19
Cx2000 AC Drive
LED
display
Address
for
comm
Parameter
name
Range
Description
Factory
defaults
Adj.
During
run
Page
H66
1)
1342
KEB action
stop level
110.0
~
145.0[%]
Sets KEB action stop level according to
level.
130.0
X
8-27
H67
1343
KEB action
gain
1
~
20000
Sets KEB action gain.
50
X
H70
1346
Frequency
reference for
accel/decel
0
~
1
0
Based on Max freq (F21)
0
X
7-12
1
Based on Delta freq.
H71
1347
Accel/Decel
time scale
0
~
2
0
Settable unit: 0.01 second.
1
O
7-12
1
Settable unit: 0.1 second.
2
Settable unit: 1 second.
H72
1348
Power on
display
0
~
17
This parameter selects the parameter to
be displayed on the keypad when the input
power is first applied.
0
O
9-2
0
Frequency command
1
Accel time
2
Decel time
3
Drive mode
4
Frequency mode
5
Multi-Step frequency 1
6
Multi-Step frequency 2
7
Multi-Step frequency 3
8
Output current
9
Motor rpm
10
Inverter DC link voltage
11
User display select (H73)
12
Fault display
13
Direction of motor rotation select
14
Output current 2
15
Motor rpm 2
16
Inverter DC link voltage 2
17
User display select 2 (H73 set)
1)
:
It is indicated when setting H64 to 1.# KEB does not operate when cut power after loading ting input (about
10% ).
Function group 2
Содержание C*2000 Series
Страница 163: ......