JOHNSON CONTROLS
83
FORM 160.72-O1 (810)
overvieW
This screen is the second of two displays for the tem-
perature alarms and trips. Each point has either an
alarm (warning) or a trip (shutdown) or both. These
points will be configured at commissioning by a quali-
fied Johnson Controls Service Technician.
displaY onlY
discharge low Temperature
Displays the Discharge Low Temperature trip point.
discharge high Temperature
Displays the Discharge High Temperature alarm and
trip points.
Compressor oil sump Temperature
Displays the Low Oil Temperature alarm and trip points
for the oil in the compressor housing.
evaporator refrigerant low Temperature
Displays the Low Refrigerant Temperature alarm and
trip points for the evaporator.
TeMperaTure alarMs and Trips sCreen (Con'T)
TEMPERATURE ALARMS AND TRIPS SCREEN
figure 33 -
shutdown offset
This value comes in operation when the low leaving
chilled liquid temperature cutout setpoint is greater
than the difference to the minimum allowable cutout
temperature which is 36° for water or the value set for
brine.
restart offset
Temperature that will permit a restart of the chiller that
cycled off because of low leaving chilled liquid tem-
perature.
prograMMaBle
Requires access level of SERVICE,
Service Technicians refer to the Service
Instructions (Form 160.72-M1) for opera-
tion instructions and explanation of all
programmable setpoints and displayed
values.
set alarms
Allows a qualified Service Technician to change any
of the alarm points shown above. Refer to the
Service
Instructions (Form 160.72-M1)
.
3
Содержание YORK OM Titan
Страница 4: ...FORM 160 72 O1 810 JOHNSON CONTROLS 4 This Page Intentionally Left Blank...
Страница 8: ...FORM 160 72 O1 810 JOHNSON CONTROLS 8 SECTION 1 INTRODUCTION This Page Intentionally Left Blank...
Страница 12: ...FORM 160 72 O1 810 JOHNSON CONTROLS 12 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 26: ...FORM 160 72 O1 810 JOHNSON CONTROLS 26 Evaporator Screen This Page Intentionally Left Blank...
Страница 52: ...FORM 160 72 O1 810 JOHNSON CONTROLS 52 Setpoints Screen This Page Intentionally Left Blank...
Страница 78: ...FORM 160 72 O1 810 JOHNSON CONTROLS 78 Options Screen This Page Intentionally Left Blank...
Страница 80: ...FORM 160 72 O1 810 JOHNSON CONTROLS 80 Drive Options Screen This Page Intentionally Left Blank...
Страница 96: ...FORM 160 72 O1 810 JOHNSON CONTROLS 96 History Screen This Page Intentionally Left Blank...
Страница 102: ...FORM 160 72 O1 810 JOHNSON CONTROLS 102 Trend Common Slots Screen This Page Intentionally Left Blank...
Страница 104: ...FORM 160 72 O1 810 JOHNSON CONTROLS 104 Custom Screen This Page Intentionally Left Blank...
Страница 118: ...FORM 160 72 O1 810 JOHNSON CONTROLS 118 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 136: ...FORM 160 72 O1 810 JOHNSON CONTROLS 136 SECTION 5 SYSTEM COMMISSIONING This Page Intentionally Left Blank...