JOHNSON CONTROLS
135
FORM 160.72-O1 (810)
5
5
7. Set the Current Limit Setpoint to 100% (unless
a percentage is desired to limit maximum cur-
rent).
8. Start the chilled water pump(s) and condenser
water pump(s) and verify evaporator and con-
denser flow switches are made.
9. Reset any existing safety trips or power failures
by moving the panel switch to the STOP/RESET
(O) position and press the CLEAR MESSAGE
button on the display. If all chiller safeties are
satisfied the display will indicate READY TO
START.
10. Move the panel switch to the START (◄) posi
-
tion. The switch is spring-loaded and will return
to the RUN (
▐
) position when released.
11. If a building automation system (BAS) is uti-
lized to start and stop the chiller remotely via
the System Cycling or Multi-Unit Cycling con-
tacts, these contacts must be closed. A Cycling
Shutdown message will appear on the display if
the contacts are open.
The start sequence shall initiate. The display will in-
dicate the operating state of the chiller as it transitions
from start-up to run mode.
sTopping uniT
To stop the unit, proceed as follows:
1. Move the panel switch to the STOP/RESET (O)
position or open the BAS Cycling contacts.
The chiller will shut down and the post-lubrica-
tion sequence will be initiated. The display will
indicate that the unit is in COASTDOWN mode.
2. Shut down the chilled water pump(s) and con-
denser water pump(s).
3. Verify that the compressor oil sump heaters are
energized.
Содержание YORK OM Titan
Страница 4: ...FORM 160 72 O1 810 JOHNSON CONTROLS 4 This Page Intentionally Left Blank...
Страница 8: ...FORM 160 72 O1 810 JOHNSON CONTROLS 8 SECTION 1 INTRODUCTION This Page Intentionally Left Blank...
Страница 12: ...FORM 160 72 O1 810 JOHNSON CONTROLS 12 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 26: ...FORM 160 72 O1 810 JOHNSON CONTROLS 26 Evaporator Screen This Page Intentionally Left Blank...
Страница 52: ...FORM 160 72 O1 810 JOHNSON CONTROLS 52 Setpoints Screen This Page Intentionally Left Blank...
Страница 78: ...FORM 160 72 O1 810 JOHNSON CONTROLS 78 Options Screen This Page Intentionally Left Blank...
Страница 80: ...FORM 160 72 O1 810 JOHNSON CONTROLS 80 Drive Options Screen This Page Intentionally Left Blank...
Страница 96: ...FORM 160 72 O1 810 JOHNSON CONTROLS 96 History Screen This Page Intentionally Left Blank...
Страница 102: ...FORM 160 72 O1 810 JOHNSON CONTROLS 102 Trend Common Slots Screen This Page Intentionally Left Blank...
Страница 104: ...FORM 160 72 O1 810 JOHNSON CONTROLS 104 Custom Screen This Page Intentionally Left Blank...
Страница 118: ...FORM 160 72 O1 810 JOHNSON CONTROLS 118 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 136: ...FORM 160 72 O1 810 JOHNSON CONTROLS 136 SECTION 5 SYSTEM COMMISSIONING This Page Intentionally Left Blank...