FORM 160.72-O1 (810)
JOHNSON CONTROLS
100
TREND SETUP SCREEN
Select the desired
Data Collection Interval
as fol-
lows:
Determine the desired time interval (in seconds),
1.
between data samples.
Calculate the full screen time display as follows:
2.
450 x Data Collection Interval = full screen
•
seconds
full screen seconds/60 = full screen minutes
•
full screen minutes/60 = full screen hours
•
full screen hours/24 = full screen days
•
Decide if the resultant sample interval and full
3.
screen display meet the requirements. If not, se-
lect a different sample interval.
select
Access Level Required: OPERATOR
This key is used to enter the slot numbers and the mini-
mum and maximum Y-axis values of each parameter
to be trended. Pressing this key places a yellow box
around Data Point 1 Slot Number. Use the
▲
and
▼
navigation keys to place the box around the value of
Data Points 1 through 6 to be changed. With the de-
sired value selected, press the
ü
key. A dialog box is
displayed permitting data entry.
data point slot # (1-6)
Access Level Required: OPERATOR
Use the SELECT key as described above and enter
the slot number from the Common Slots Screen or
Master Slot Number List of the desired parameter to
be trended. The selected parameter description will be
displayed for the Data Point. Setting this slot number
to zero will disable trending for that particular Data
Point. Any or all points can be disabled.
data point Min (1-6)
Access Level Required: OPERATOR
Only displayed if the Associated Slot Number is not
Zero. This is the minimum value displayed for the
Y-axis. Selecting a parameter for a Data Point sets this
to the default value, which is the lowest value allowed
for that parameter. It can be changed to a value that
provides a more appropriate resolution for the param-
eter being monitored. To change, use the SELECT key
as described above and enter the desired value. The
value must always be set to a value less than the Data
Point Max. Otherwise, a red graph is displayed on the
Trend Screen with the words
TREND MAX MUST
BE > TREND MIN
. If the parameter selected for this
data point is a digital type (on/off), this value must be
set to zero (0). Zero indicates the OFF state.
data point Max (1-6)
Access Level Required: OPERATOR
Only displayed if the associated slot number is not
zero. This is the maximum value displayed for the
Y-axis. Selecting a parameter for a Data Point sets this
to the default value, which is the highest value allowed
for that parameter. It can be changed to a value that
provides a more appropriate resolution for the param-
eter being monitored. To change, use the
SELECT
key
as described above and enter the desired value. The
value must always be set to a value greater than the
Data Point Min. Otherwise, a red graph is displayed on
the Trend Screen with the words TREND MAX MUST
BE > TREND MIN. There are 20 Y-axis divisions. If a
MIN-MAX span is selected that is not evenly divided
by 20, the Program will automatically select the next
higher MAX value that makes the span evenly divided
by 20. For example, if 0.0 is selected as the MIN and
69.0 is selected as the MAX, the Program will insert
70.0 as the MAX value. If the parameter selected for
this data point is a digital type (on/off), this value must
be set to one (1). One indicates the on state.
navigaTion
home
Returns user to Home Screen.
Trending
Returns user to Trending Screen.
slot numbers
Causes a jump to a subscreen that lists the slot num-
bers of the most commonly monitored parameters. The
desired parameters to be plotted are selected from this
screen.
Содержание YORK OM Titan
Страница 4: ...FORM 160 72 O1 810 JOHNSON CONTROLS 4 This Page Intentionally Left Blank...
Страница 8: ...FORM 160 72 O1 810 JOHNSON CONTROLS 8 SECTION 1 INTRODUCTION This Page Intentionally Left Blank...
Страница 12: ...FORM 160 72 O1 810 JOHNSON CONTROLS 12 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 26: ...FORM 160 72 O1 810 JOHNSON CONTROLS 26 Evaporator Screen This Page Intentionally Left Blank...
Страница 52: ...FORM 160 72 O1 810 JOHNSON CONTROLS 52 Setpoints Screen This Page Intentionally Left Blank...
Страница 78: ...FORM 160 72 O1 810 JOHNSON CONTROLS 78 Options Screen This Page Intentionally Left Blank...
Страница 80: ...FORM 160 72 O1 810 JOHNSON CONTROLS 80 Drive Options Screen This Page Intentionally Left Blank...
Страница 96: ...FORM 160 72 O1 810 JOHNSON CONTROLS 96 History Screen This Page Intentionally Left Blank...
Страница 102: ...FORM 160 72 O1 810 JOHNSON CONTROLS 102 Trend Common Slots Screen This Page Intentionally Left Blank...
Страница 104: ...FORM 160 72 O1 810 JOHNSON CONTROLS 104 Custom Screen This Page Intentionally Left Blank...
Страница 118: ...FORM 160 72 O1 810 JOHNSON CONTROLS 118 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 136: ...FORM 160 72 O1 810 JOHNSON CONTROLS 136 SECTION 5 SYSTEM COMMISSIONING This Page Intentionally Left Blank...