MOTOR SCREEN
auxiliary start Contact (led)
A back-up LED that indicates when the safety contact
in the starter is closed.
length of last run
Displays the time of the last chiller run in
Day:Hr:Min:Sec format.
prograMMaBle
rated fla
Access Level Required: SERVICE
The rated FLA of the compressor motor used to de-
termine the percentage of full load amps displayed.
Service Technicians refer to the
Service Instructions
(Form 160.72-M1).
rated flKW
Access Level Required: SERVICE
The rated Full Load Kilowatts used to determine the
percentage of full load kilowatts displayed. This calcu-
lation will only be present if the Kilowatts sensor has
been enabled. Service Technicians refer to the
Service
Instructions (Form 160.72-M1)
.
local demand limit
Access Level Required: OPERATOR
Allows the operator to change the Demand Setpoint
from 0 % to 100 %. This will be the Current Limit
Setpoint or the Power Limit Setpoint depending on the
configuration established at commissioning. Service
Technicians refer to the
Service Instructions (Form
160.72-M1)
.
navigaTion
home
Access Level Required: VIEW
Returns user to Home Screen.
gearbox
Access Level Required: VIEW
Moves to the gearbox screen that shows temperatures
and pressures for the gearbox oil lubrication system
and allows manual control of the auxiliary oil pump,
if equipped.
anti-recycle setpoints
Access Level Required: VIEW
Moves to the anti-recycle setpoints screen that shows
timers and counters for Anti-Recycle operation.
Содержание YORK OM Titan
Страница 4: ...FORM 160 72 O1 810 JOHNSON CONTROLS 4 This Page Intentionally Left Blank...
Страница 8: ...FORM 160 72 O1 810 JOHNSON CONTROLS 8 SECTION 1 INTRODUCTION This Page Intentionally Left Blank...
Страница 12: ...FORM 160 72 O1 810 JOHNSON CONTROLS 12 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 26: ...FORM 160 72 O1 810 JOHNSON CONTROLS 26 Evaporator Screen This Page Intentionally Left Blank...
Страница 52: ...FORM 160 72 O1 810 JOHNSON CONTROLS 52 Setpoints Screen This Page Intentionally Left Blank...
Страница 78: ...FORM 160 72 O1 810 JOHNSON CONTROLS 78 Options Screen This Page Intentionally Left Blank...
Страница 80: ...FORM 160 72 O1 810 JOHNSON CONTROLS 80 Drive Options Screen This Page Intentionally Left Blank...
Страница 96: ...FORM 160 72 O1 810 JOHNSON CONTROLS 96 History Screen This Page Intentionally Left Blank...
Страница 102: ...FORM 160 72 O1 810 JOHNSON CONTROLS 102 Trend Common Slots Screen This Page Intentionally Left Blank...
Страница 104: ...FORM 160 72 O1 810 JOHNSON CONTROLS 104 Custom Screen This Page Intentionally Left Blank...
Страница 118: ...FORM 160 72 O1 810 JOHNSON CONTROLS 118 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 136: ...FORM 160 72 O1 810 JOHNSON CONTROLS 136 SECTION 5 SYSTEM COMMISSIONING This Page Intentionally Left Blank...