TEMPERATURE ALARMS AND TRIPS SCREEN
Compressor Thrust Bearing high oil Tem-
perature
Displays the High Oil Temperature alarm and trip point
for the Thrust Bearing of the compressor.
gearbox high oil Temperature
Displays the High Oil Temperature alarm and trip point
for the oil in the gearbox.
Compressor oil low Temperature
Displays the Low Oil Temperature trip point for the
main oil supply to the compressor.
Compressor oil low differential Temperature
Displays the temperature differential between the sump
oil and the condenser saturation pressure/temperature
that will prevent the chiller from starting if the system
has been shutdown for less than 30 minutes.
Compressor oil Warm start differential
Temperature offset
Displays the temperature differential between the sump
oil and the condenser saturation pressure/temperature
that will prevent the chiller from starting if the system
has been shutdown for more than 30 minutes.
Compressor oil high Temperature
Displays the High Oil Temperature trip point for the oil
in the compressor housing.
prograMMaBle
Requires access level of SERVICE.
Service Technicians refer to the Service
Instructions (Form 160.72-M1) for opera-
tion instructions and explanation of all
programmable setpoints and displayed
values.
set alarms
Allows a qualified Service Technician to change any
of the alarm points shown above. Refer to the
Service
Instructions (Form 160.72-M1)
.
set Trips
Allows a qualified Service Technician to change any
of the trip points shown above. Refer to the
Service
Instructions (Form 160.72-M1)
.
navigaTion
home
Access Level Required: VIEW
Returns user to Home Screen.
setup
Access Level Required: VIEW
Returns the user to the Setup Screen.
Temperature alarms/Trips
Access Level Required: VIEW
Returns to the Temperature Alarms/Trips Screen.
pressure alarms/Trips
Access Level Required: VIEW
Moves directly to the Pressure Alarms and Trips
Screen.
Time alarms/Trips
Access Level Required: VIEW
Moves directly to the Time Alarms and Trips Screen.
Misc alarms/Trips
Access Level Required: VIEW
Moves directly to the Miscellaneous Alarms and Trips
Screen.
page down
Access Level Required: VIEW
Moves to the second screen of the Temperature Alarms
and Trips Screen.
Содержание YORK OM Titan
Страница 4: ...FORM 160 72 O1 810 JOHNSON CONTROLS 4 This Page Intentionally Left Blank...
Страница 8: ...FORM 160 72 O1 810 JOHNSON CONTROLS 8 SECTION 1 INTRODUCTION This Page Intentionally Left Blank...
Страница 12: ...FORM 160 72 O1 810 JOHNSON CONTROLS 12 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 26: ...FORM 160 72 O1 810 JOHNSON CONTROLS 26 Evaporator Screen This Page Intentionally Left Blank...
Страница 52: ...FORM 160 72 O1 810 JOHNSON CONTROLS 52 Setpoints Screen This Page Intentionally Left Blank...
Страница 78: ...FORM 160 72 O1 810 JOHNSON CONTROLS 78 Options Screen This Page Intentionally Left Blank...
Страница 80: ...FORM 160 72 O1 810 JOHNSON CONTROLS 80 Drive Options Screen This Page Intentionally Left Blank...
Страница 96: ...FORM 160 72 O1 810 JOHNSON CONTROLS 96 History Screen This Page Intentionally Left Blank...
Страница 102: ...FORM 160 72 O1 810 JOHNSON CONTROLS 102 Trend Common Slots Screen This Page Intentionally Left Blank...
Страница 104: ...FORM 160 72 O1 810 JOHNSON CONTROLS 104 Custom Screen This Page Intentionally Left Blank...
Страница 118: ...FORM 160 72 O1 810 JOHNSON CONTROLS 118 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 136: ...FORM 160 72 O1 810 JOHNSON CONTROLS 136 SECTION 5 SYSTEM COMMISSIONING This Page Intentionally Left Blank...