INTERSTAGE VALVE SCREEN
interstage valve Control Mode
Indicates whether the Interstage Valve is under auto-
matic or manual control.
prograMMaBle
Requires access level of SERVICE.
Service Technicians refer to the Service
Instructions (Form 160.72-M1) for opera-
tion instructions and explanation of all
programmable setpoints and displayed
values.
[interstage valve Control] raise (Manual)
Access Level Required: SERVICE
This key allows the Service Technician to open the
valve in increments of 1% or more from its current po-
sition.
[interstage valve Control] lower (Manual)
Access Level Required: SERVICE
This key allows the Service Technician to close the
valve in increments of 1% or more from its current po-
sition.
[interstage valve Control] set (Manual)
Access Level Required: SERVICE
This key allows the Service Technician to input a value
from 0 to 100 % to position the valve immediately.
[interstage valve Control] switch to Manual
Access Level Required: SERVICE
This key toggles between Switch to Manual and
Switch to Auto to allow for control of the Hot Gas By-
pass Valve. The Interstage Valve Control Mode display
will indicate the control mode of the valve and prevent
transfer of the mode from manual to auto when the cal-
culated auto position and the manual position differ by
more than 5%. This will be indicated by the SWITCH
TO AUTO button color changing from green to red
mode from manual to auto when the calculated auto
position and the manual position differ by more than
5%. This will be indicated by the SWITCH TO AUTO
button color changing from green to red.
navigaTion
home
Access Level Required: VIEW
Returns user to Home Screen.
Compressor
Access Level Required: VIEW
Returns user to the Compressor Screen.
Содержание YORK OM Titan
Страница 4: ...FORM 160 72 O1 810 JOHNSON CONTROLS 4 This Page Intentionally Left Blank...
Страница 8: ...FORM 160 72 O1 810 JOHNSON CONTROLS 8 SECTION 1 INTRODUCTION This Page Intentionally Left Blank...
Страница 12: ...FORM 160 72 O1 810 JOHNSON CONTROLS 12 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 26: ...FORM 160 72 O1 810 JOHNSON CONTROLS 26 Evaporator Screen This Page Intentionally Left Blank...
Страница 52: ...FORM 160 72 O1 810 JOHNSON CONTROLS 52 Setpoints Screen This Page Intentionally Left Blank...
Страница 78: ...FORM 160 72 O1 810 JOHNSON CONTROLS 78 Options Screen This Page Intentionally Left Blank...
Страница 80: ...FORM 160 72 O1 810 JOHNSON CONTROLS 80 Drive Options Screen This Page Intentionally Left Blank...
Страница 96: ...FORM 160 72 O1 810 JOHNSON CONTROLS 96 History Screen This Page Intentionally Left Blank...
Страница 102: ...FORM 160 72 O1 810 JOHNSON CONTROLS 102 Trend Common Slots Screen This Page Intentionally Left Blank...
Страница 104: ...FORM 160 72 O1 810 JOHNSON CONTROLS 104 Custom Screen This Page Intentionally Left Blank...
Страница 118: ...FORM 160 72 O1 810 JOHNSON CONTROLS 118 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 136: ...FORM 160 72 O1 810 JOHNSON CONTROLS 136 SECTION 5 SYSTEM COMMISSIONING This Page Intentionally Left Blank...