JOHNSON CONTROLS
93
FORM 160.72-O1 (810)
overvieW
This screen allows the user to browse through the faults.
In order to get a more thorough reporting of the system
conditions at the time of the recorded shutdown, move to
the subscreen
HISTORY DETAILS
. The user may use
the
Select Fault
button to select the history to view. At
this point the
View Details
button is used to jump to a
subscreen containing stored chiller parameters values at
the time of the shutdown. Additionally, the
Print History
button can be used to generate a hard-copy report of the
parameter values at the time of the shutdown.
displaY onlY
last normal shutdown
This window displays the date and time and the de-
scription of the last normal shutdown. A normal shut-
down is defined as:
Local (Panel rocker switch)
•
Remote (Digital, Analog or BAS)
•
hisTorY sCreen
HISTORy SCREEN
figure 38 -
last fault While running
This window displays the date and time and the de-
scription of the last safety or cycling shutdown while
the system was running.
last Ten faults
This window displays a chronological listing (most
recent first) of the date and time and the description
of the last ten safety or cycling shutdowns that occur
while the system is running or stopped.
prograMMaBle
print all histories
Access Level Required: VIEW
This generates a report listing the status of the chill-
er parameters at the time of each of the stored shut-
downs.
3
Содержание YORK OM Titan
Страница 4: ...FORM 160 72 O1 810 JOHNSON CONTROLS 4 This Page Intentionally Left Blank...
Страница 8: ...FORM 160 72 O1 810 JOHNSON CONTROLS 8 SECTION 1 INTRODUCTION This Page Intentionally Left Blank...
Страница 12: ...FORM 160 72 O1 810 JOHNSON CONTROLS 12 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 26: ...FORM 160 72 O1 810 JOHNSON CONTROLS 26 Evaporator Screen This Page Intentionally Left Blank...
Страница 52: ...FORM 160 72 O1 810 JOHNSON CONTROLS 52 Setpoints Screen This Page Intentionally Left Blank...
Страница 78: ...FORM 160 72 O1 810 JOHNSON CONTROLS 78 Options Screen This Page Intentionally Left Blank...
Страница 80: ...FORM 160 72 O1 810 JOHNSON CONTROLS 80 Drive Options Screen This Page Intentionally Left Blank...
Страница 96: ...FORM 160 72 O1 810 JOHNSON CONTROLS 96 History Screen This Page Intentionally Left Blank...
Страница 102: ...FORM 160 72 O1 810 JOHNSON CONTROLS 102 Trend Common Slots Screen This Page Intentionally Left Blank...
Страница 104: ...FORM 160 72 O1 810 JOHNSON CONTROLS 104 Custom Screen This Page Intentionally Left Blank...
Страница 118: ...FORM 160 72 O1 810 JOHNSON CONTROLS 118 SECTION 3 OPTIVIEW CONTROL CENTER This Page Intentionally Left Blank...
Страница 136: ...FORM 160 72 O1 810 JOHNSON CONTROLS 136 SECTION 5 SYSTEM COMMISSIONING This Page Intentionally Left Blank...