Fridgewatch 2100 Controller Mk4
Section 3
Publication 3-58
Issue 1.1 : 01/08
Page 47 of 152
F
UNCTION
T
ERMINALS
R
EMARKS
N
2
L
o
o
180
181
Oil Heaters
Maximum combined
heater current
MUST
NOT
exceed 5 Amp
240/110 V ac
N
2
L
o
o
182
183
4
Oil separator/reservoir oil heaters energise when the
last compressor stops; de-energies when the first
compressor starts.
If the combined heater current exceeds 5 Amp, the
heaters should be switched by a secondary contact of
the main compressor starter.
1
Common Liquid Line Solenoid Valve
240/110 V ac
N
3
L
o
o
178
179
Energise (open) when the first compressor starts,
de-energise (close) when the last compressor stops.
1
Oil Injection Solenoid Valve
240/110 V ac
N
3
L
o
o
184
185
Energise (open) when the compressor starts,
de-energise (close) when the compressor stops.
1,5
Economiser Solenoid Valve
240/110 V ac
N
3
L
o
o
184A
185A
Located in the liquid line through the economiser to the
evaporator; refer to Fig 12.
Energise (open) when the compressor starts,
de-energise (close) when the compressor stops.
1
Liquid Injection Solenoid Valve
240/110 V ac
N
3
L
o
o
186
187
Energise (open) when the compressor starts,
de-energise (close) when the compressor stops.
1
Economiser Solenoid Valve
240/110 V ac
N
L
o
o
188
189
Located in the liquid line before the regulator feeding
the economiser; refer to Fig 12.
Energise (open) when compressor capacity > 50 %,
de-energise (close) when capacity < 50 %.
When using an LVDT for slide valve position, S63 = 3
or 4, refer to S116 and S117 descriptions.
Capacity Control Solenoids (4-Way Valve
Illustrated)
N
L
o
o
190
191
240/110 V ac
N
L
o
o
192
193
Different solenoid valve types require different
energisation patterns; refer to Table 12.
Energisation patterns for compressors 1, 2 and 3 are
independently set by settings S62, S107 and S108
respectively.
Terminal prefix 1 = compressor 1. This prefix does not physically appear on the card.
Relays outputs are either 110 V ac or 240 V ac.
Contacts are rated at 8 Amp continuous/3 Amp inductive at 250 V ac.
1
If fitted, depends on the application.
2
Terminals 181 and 183 share one 8 Amp/3 Amp contact.
3
Terminals 185, 185A and 187 share one 8 Amp/3 Amp contact.
4
If Fridgewatch 2100 controls more than one compressor package unit, each with its own oil separator/reservoir and oil
heaters,
DO NOT
use terminals 180 to 183 to control the oil heaters; use a secondary contact from each individual
compressor motor contactor.
5
For multi-compressor applications using individual economisers; refer to Fig 12. Can be used to control an evaporator
liquid line solenoid valve.
Fig 18 Wiring Connections to 3SCOP1 Relay Outputs Card for Compressor 1
Solenoid A (load)
on 4-way valve
S
S
S
Solenoid B (unload)
on 4-way valve
S
S
S
S