Fridgewatch 2100 Controller Mk4
Publication 3-58
Section 3
Page 148 of 152
Issue 1.1 : 01/08
17.
Appendix 4 - Start-up Timing Diagram
Fig 34 show the sequence of events as a HallScrew compressor starts
under the control of a Fridgewatch 2100 Controller Mk4. This is the only
sequence approved by J & E Hall International.
Time
Start point: i.e. a start is available and a decision has been made to start. HP, LP and
user
1
(E24) cut-outs OK; discharge, motor
1
and oil high temperature thermistors OK.
Home Page
→
Status: Available
Status: Available changes to Starting
Starts per hour timer (60
divided by S49) minutes
Trip E33 Lost Run Signal, if running signal
disappears before Fridgewatch 2100 signals
the compressor to stop
1
If fitted, depends on the application.
Concluded on next page
Fig 34 Compressor Start-up Timing Diagram
If slide valve(s) not at
minimum load, continue
minimum load signal for
120 seconds
Auxiliaries start
timer initiated, set
to S50 value
Trip E8 Failed to Unload, if
minimum load signal not attained
Trip E30 Auxiliaries Failed to Start,
if auxiliaries fail to start
Compressor running signal
received (via x25)
A
B
Send start signal to
compressor (via x24)
Compressor start timer
initiated, set to S51 value
Trip E9 Failed to Start, if
compressor fails to start
Compressor
allowed to start
Set starts per hour timer
‘At minimum load’ signal
received (via x30)
Check if slide
valve(s) are at
minimum load
Trip E34 Auxiliaries Lost Run Signal if
auxiliaries running signal disappears
Auxiliaries running signal
received (via x28)
Send start signal to
auxiliaries (via x27)