14.
Appendix 1 - Measured Points Reference
P
OSSIBLE
A
PPLICATION
P
OINT
A
BBREVIATED
D
ESCRIPTION
F
ULL
D
ESCRIPTION
Co
ntro
l
Disp
lay
Lim
it
in
g
Tri
p
U
NITS
P1
1
Temp
Measured
temperature
X X X X
°
C
P2
1
Press
Measured
pressure
X X X X bar
g
P3
Hrs Run
Hours run
X
hour
x
10
P4
1
SVP Slide
valve
position
X X %
P5 Motor
Motor
current
X X Amp
1
Most common use shown.
Table 19 Measured Points Quick-Reference
1
W
IRING
C
ONNECTIONS
P
OINT
F
UNCTION
A
SSOCIATED
S
ETTINGS
C
ARD
A
NIN
T
ERMINALS
Read/display S43
Define P1 as the Set Point and/or Start
Value and/or Stop Value
S46 to S48
Set Point/Start Value/Stop Value
S1 to S3 inclusive, S20 to
S31 inclusive
Control parameters
S4 to S19 inclusive, S60 and
S73
P1
Limiting and/or trip on P1 (E12)
S90 to S93 inclusive
3MIO1 Anin
1 101/104
Read/display and scale
S44 and S45
Define P2 as the Set Point and/or Start
Value and/or Stop Value
S46 to S48 inclusive
Set Point/Start Value/Stop Value
S1 to S3 inclusive, S20 to
S31 inclusive
Control parameters
S4 to S19 inclusive, S60 and
S73
P2
Limiting and/or trip on P2 (E13)
S94 to S97 inclusive
3MIO1 Anin
2 105/108
P3
Initialise hours run after changing
RAMP4 processor card
S56 to S58 inclusive
-
-
-
Read/display S63
Scale S84
and
S85
P4
Limiting
S86 to S88 inclusive
Comp 1
3MIO1
Comps
2 and 3
3MIO2
Comp 1
Anin 3
Comps
2 and 3
Anin 1
Comp 1
151/154
Comps
2 and 3
x01/x04
Read/display
S64, S67 and S70
P5
Limiting
S65, S66, S68, S69, S71
and S72
Comp 1
3MIO1
Comps
2 and 3
3MIO2
Comp 1
Anin 4
Comps
2 and 3
Anin 2
Comp 1
155/156
Comps
2 and 3
x05/x06
1
Terminal prefix x = 2 for compressor 2, x = 3 for compressor 3; refer to Fig 4. This prefix does not physically appear on
the card.
Table 20 Measured Points Function and Settings Cross-Reference