Fridgewatch 2100 Controller Mk4
Section 3
Publication 3-58
Issue 1.1 : 01/08
Page 61 of 152
F
UNCTION
T
ERMINALS
R
EMARKS
From Another Fridgewatch 2100 or 2000
Controller in Master/Slave Configuration
Digital Inputs From Another FW 2100 or 2000
Controller in Master/Slave Configuration: S19 = 1
o
o
o
o
o
o
x35
x36
x37
x38
x39
x40
235 =
236 =
237 =
238 =
239 =
x40 =
From slave (if in master/slave configuration).
From slave (if in master/slave configuration).
From slave (if in master/slave configuration).
DO NOT
use this terminal.
To Fridgewatch Auto Controller or System
Controller
Digital Inputs Fridgewatch Auto Controller or
System Controller S19 = 0
o
o
o
x41
x42
x43
x41 =
242 =
342 =
243 =
343 =
Link to terminal 249 if driving relays.
One or more compressors at maximum load.
Two or more compressors at maximum load.
Two or more compressors running.
Three compressors running.
or Digital Outputs to a Control Device
x41 =
242 =
342 =
243 =
343 =
248 =
249 =
250 =
Link to terminal 249 if driving relays.
One or more compressors at maximum load.
Two or more compressors at maximum load.
Two or more compressors running.
Three compressors running.
DO NOT
use this terminal.
+24 V supply to drive relays.
0 V.
o
o
o
o
o
o
x41
x42
x43
x48
x49
x50
NOTE: when relays
2
are used, reverse bias diodes
3
MUST be fitted.
Terminal prefix: x = 2 for compressor 2, x = 3 for compressor 3; refer to Fig 4. This prefix does not physically appear on
the card.
1
If fitted, depends on the application.
2
Relays must be low consumption type, 40 mA maximum, Omron LY2 or similar (RS Components part number 329-799).
3
Diode type 1N4004
MUST
be fitted. Connect as illustrated in Fig 11 to ensure correct polarity.
Fig 26 (continued) Wiring Connections to 3MIO2 Input/Output Card for Compressors 2 and 3
Slave running
Slave at minimum load
Slave at maximum load
Link
Do not use
Relays
2
(40 mA max) with reverse
bias diodes
3
type 1N4004
Run signal
relay
2
Intermediate
load 1 relay
2
+24 V dc
Intermediate load signal
Run signal
Link terminals 235 and 236.