Fridgewatch 2100 Controller Mk4
Section 3
Publication 3-58
Issue 1.1 : 01/08
Page 59 of 152
F
UNCTION
T
ERMINALS
R
EMARKS
LP Cut-out
O
o
x17
x18
LP cut-out contacts open on fault condition.
Fridgewatch 2100 displays a trip: event code E5 LP
Cut-out.
Check jumper connection J18 on the 3MIO2 card; refer
to Fig 25.
Oil Low Level Opto-Electronic Liquid Sensor
Independent Oil Separators
o
o
x19
x20
or
o
o
x19
x20
or Oil Low Level Switch
o
o
x19
x20
Refer to Fig 1.
If one oil separator and one opto sensor or level switch
are used, wire to the 3MIO1 card; refer to Fig 24. Link
terminals x19 and x20 and set S83 = 0.
If each compressor has its own oil separator, opto
sensor or level switch, wire compressor 1 to the 3MIO1
card (refer to Fig 24), wire compressor 2 to card 2,
compressor 3 to card 3 and set S83 = 1.
If an oil level switch is fitted instead of an opto sensor,
the opto sensor interface is not used and must be
disconnected from terminals x19 and x20. The oil level
switch (contacts open on fault condition) is wired
directly to terminals x19 and x20.
Check jumper connection J18 on the 3MIO2 card; refer
to Fig 25.
If neither an oil level switch nor oil level sensor are
fitted, link terminals x19 and x20.
Opto sensor interface unit oil level switch contacts
open on fault condition (internally timed by Fridgewatch
2100 to prevent nuisance tripping). Fridgewatch 2100
displays a trip: event code E4 Low Oil Level in
Separator/Reservoir.
Oil Differential Pressure Switch (ODPS) or
Oil Flow Switch
o
o
x21
x22
Switch contacts open on fault condition (internally
timed by Fridgewatch 2100 to prevent nuisance
tripping).
Check jumper connection J20 on the 3MIO1 card; refer
to Fig 23.
ODPS or flow switch contacts open on fault condition.
Fridgewatch 2100 displays a trip: event code E7 Low
Oil Injection Differential Pressure (ODPS).
Terminal prefix: x = 2 for compressor 2, x = 3 for compressor 3; refer to Fig 4. This prefix does not physically appear on
the card.
1
If fitted, depends on the application.
2
Relays must be low consumption type, 40 mA maximum, Omron LY2 or similar (RS Components part number 329-799).
3
Diode type 1N4004
MUST
be fitted. Connect as illustrated in Fig 11 to ensure correct polarity.
Fig 26 (continued) Wiring Connections to 3MIO2 Input/Output Card for Compressors 2 and 3
Link
165/166
WHITE
BROWN
GREEN
165
166
167
168
OPTO SENSOR
INTERFACE UNIT
Wires from
Paw Phonix
opto sensor in
oil separator/
reservoir
RED
GREEN
BLUE
Wires from
AC & R opto
sensor in oil
separator/
reservoir
OPTO SENSOR
INTERFACE UNIT
RED
GREEN
BLUE
ORANGE
WHITE
BLACK
Link
167/168
165
166
167
168