Fridgewatch 2100 Controller Mk4
Section 3
Publication 3-58
Issue 1.1 : 01/08
Page 67 of 152
Scroll mode flashes the Sxx index and only allows scrolling
up/down settings.
Edit mode flashes the settings value to permit the value to be
modified.
Collectively, the
and
buttons are referred to as the Navigation
Buttons.
8.8.7.
Scroll Up - Raise Setting - Start/Load Compressor (Manual Control
Only)
SCROLL UP - RAISE SETTING - START/LOAD COMPRESSOR (MANUAL
CONTROL ONLY)
This button has three separate functions depending on the position of the
Supervisor Keyswitch.
With the Supervisor Key in the Locked position the
navigation button is
used to scroll through the menu pages.
In any menu page, press the
button to scroll up through the menu.
With the Supervisor Key in the Unlocked position, the
navigation button
has two separate functions
Start/Load Compressor (Manual Control Only)
With ‘manual’ start/stop mode selected and the compressor stopped, turn
the Supervisor Key to the Unlocked position and press the
button to
start the compressor if it is available to start. There may be a short delay
before the compressor is seen or heard to start. On the Home page
display the message ‘Starting’ appears next to the Status heading.
With ‘manual’ capacity control selected, after S52 Oil Injection Differential
Pressure (ODP1) Delay Time has expired, pressing the
button once
more begins to load the compressor. A single, short press of the
button sends a load pulse to the compressor slide valves, duration S141
seconds, while pressing and holding down the button sends a string of
pulses.
In a multi-compressor application, when the controlled compressor
reaches maximum capacity, a further press of the
button starts the
next available compressor in the running order priority (if available to
start).
In a master/slave configuration, when all the compressors controlled by
the master Fridgewatch 2100 Controller have reached maximum
capacity, a further press of the
button starts the first compressor in the
slave compressor running order (if available to start).
Raise Setting Value
The other function of the
button is to raise the value of a setting.
Having selected the appropriate setting as described in Fig 28 or Fig 29,
and with the Supervisor Keyswitch in the Unlocked position, pressing the
button raises the integer or decimal place value of the setting.