Fridgewatch 2100 Controller Mk4
Publication 3-58
Section 3
Page 104 of 152
Issue 1.1 : 01/08
H
ALL
S
CREW
C
OMPRESSOR
S
ERIES
F
RIDGEWATCH
2100
3SCOP1
R
ELAY
C
ARD
C
HANNELS
AND
T
ERMINAL
P
AIRS
4-W
AY
S
OLENOID
V
ALVE
:
2
S
OLENOIDS
1,
3
NC
(S62
=
0)
C
APACITY
C
ONTROL
A
CTION
S
OLENOID
A
X
90/
X
91
S
OLENOID
B
X
92/
X
93
Load compressor
Energise
De-energise
Unload compressor
De-energise
Energise
Hold slide valve position
De-energise
HS 18 to HS 235
2000 Series:
HS 2018 to HS 2235
2100 Series:
HS 2116 to HS 2120
If a 4-way valve is used but S62 = 1 or 2 is set by mistake, both
solenoid valve coils will be energised at the same time and will
eventually burn out.
S
EPARATE
S
OLENOID
V
ALVES
:
4
OFF
1
NC
(S62
=
0)
C
APACITY
C
ONTROL
A
CTION
3
S
OLENOIDS
X
90/
X
91
3
S
OLENOIDS
X
92/
X
93
Load compressor
Energise
De-energise
Unload compressor
De-energise
Energise
HS 18 to HS 235
2000 Series:
HS 2018 to HS 2235
2100 Series:
HS 2116 to HS 2120
Hold slide valve position
De-energise
S
EPARATE
S
OLENOID
V
ALVES
:
2
OFF
1
NC
(S62
=
0)
C
APACITY
C
ONTROL
A
CTION
3
S
OLENOID
A
X
90/
X
91
3
S
OLENOID
B
X
92/
X
93
Load compressor
Energise
De-energise
Unload compressor
De-energise
Energise
3100 New
Series:
HS 3118 to
HS 3122
3200 Series:
HS 3216 to
HS 3221
4200 Series:
HS 4221 to
HS 4223
Hold slide valve position
De-energise
S
EPARATE
S
OLENOID
V
ALVES
:
2
OFF
1
NC
AND
2
OFF
2
NO
(S62
=
1)
C
APACITY
C
ONTROL
A
CTION
1,
3
NC
S
OLENOIDS
W
AND
Z
X
90/
X
91
2,
3
NO
S
OLENOIDS
X
AND
Y
X
92/
X
93
Load compressor
Energise
Unload compressor
De-energise
2000 Series: HS 2018 to HS 2022
Hold slide valve position
De-energise
Energise
S
EPARATE
S
OLENOID
V
ALVES
:
2
OFF
1
NC
(S62
=
2)
C
APACITY
C
ONTROL
A
CTION
1,
3
NC
S
OLENOID
X
90/
X
91
1,
3
NC
S
OLENOID
X
92/
X
93
Load compressor
Energise
Unload compressor
De-energise
Energise
3100 Old Series: HS 3116 to HS 3120
Hold slide valve position
De-energise
1
NC = normally closed (energise to open).
2
NO = normally open (energise to close).
3
Terminal prefix x = 1 for compressor 1, x = 2 for compressor 2, x = 3 for compressor 3; refer to Fig 4. This prefix does not
physically appear on the card.
Table 12 Capacity Control Valve Application and Operation