Appendix 2 - Event Codes E1/E47 Quick-Reference
E
VENT
A
BBREVIATED
D
ESCRIPTION
F
ULL
D
ESCRIPTION
E1
High Motor Temp
High motor temperature
E2
High Discharge Temp
High discharge temperature
E3 Not used
E4
Low Oil Level in Sep/Res
Low oil level in separator/reservoir
E5
LP cut-out (or FS2 blown)
LP cut-out (or fuse FS2 blown)
E6
HP cut-out
HP cut-out
E7
Low Oil Inject Diff Press
Low oil injection differential pressure (ODP1)
E8
Comp Failed to Unload
Compressor failed to unload
E9
Comp Failed to Start
Compressor failed to start
E10 and E11 Not used
E12
Low P1 (Temperature)
Low P1 (temperature)
E13
Low P2 (Pressure)
Low P2 (pressure)
E14
High or Low P6 Temp/Press
1
High or low P6 (pressure or temperature).
E15 to E23 Not used
E24
Cut-Out
Cut-out (not allocated)
E25 to E29 Not used
E30
Aux/Cond Cool Pump Fail
Auxiliaries/condenser cooling water pump failed to start
E31 and E32 Not used
E33
Compressor Lost Running
Compressor lost running signal
E34
Aux/Cond Pump Lost Running
Auxiliaries/condenser cooling water pump lost running signal
E35 to E40 Not used
E41
P1 Temp 3MIO1 OR/Fail
P1 (temperature input on 3MIO1 card) over-range or failed
E42
P2 Press 3MIO1 OR/Fail
P2 (pressure input on 3MIO1 card) over-range or failed
E43
Digital Output 3MIO1 Fail
Digital output failure on 3MIO1 card
E44
Digital Input 3MIO1 Fail
Digital input failure on 3MIO1 card
E45
Digital Input 3MIO1 Fail
Digital input failure on 3MIO1 card
E46
P4 LVDT 3MIO1 OR/Fail
P4 (LVDT input on 3MIO1 card) over-range or failed
E47
P5 Motor Current OR/Fail
P5 (motor current input on 3MIO1 card) over-range or failed
1
Refer to Table 5 E14 High or Low P6 (Pressure or Temperature).
2
Terminal prefix x = 1 for compressor 1, x = 2 for compressor 2, x = 3 for compressor 3; refer to Fig 4.
This prefix does not physically appear on the card.
1
For a detailed explanation refer to 10. Event Codes.
2
The type of event code:
Trip = Stops the plant. Information = Information only.
3
The method of reset:
Manual (Trip) = The trip must be reset by the operator before the plant can restart.
Self-clearing = Operator intervention not required.
4
Depends on the application and/or operating mode.