Fridgewatch 2100 Controller Mk4
Publication 3-58
Section 3
Page 126 of 152
Issue 1.1 : 01/08
Select ‘manual’ start/stop – ‘manual’ capacity control mode; refer to 9.7. Changing the Operating
Mode.
CALIBRATION
Min
SVP
786
←
Supervisor
Mode
to
Start
Calibration
Turn
Key
to
Normal
to
Save
Calibration
Change Operator Setting S36 = 2. When the Supervisor Key is turned to the Locked position to
accept the new value the screen above is displayed.
Turn the Supervisor Key to the Unlocked position. The current value of analogue input P4
appears in the display.
Press the
button to unload the compressor until you are sure the slide valves have reached
the minimum load position.
Turn the Supervisor Key to the Locked position to ‘fix’ the minimum calibration, i.e. tell
Fridgewatch 2100 that the signal it is currently receiving into the P4 analogue input is the value it
should interpret as the minimum load position and display 0 %. An arrow
←
appears to the right
of the value to indicate that the calibration has been fixed.
Fridgewatch automatically returns S36 = 0 when the minimum calibration is fixed.
CALIBRATION
Max
SVP
4011
←
Supervisor Mode to Start Calibration
Turn Key to Normal to Save Calibration
Change Operator Setting S36 = 3. When the Supervisor Key is turned to the Locked position to
accept the new value the screen above is displayed.
Turn the Supervisor Key to the Unlocked position. The current value of analogue input P4
appears in the display.
Press the
button to load the compressor until you are sure the slide valves have reached the
maximum load position.
Turn the Supervisor Key to the Locked position to ‘fix’ the maximum calibration, i.e. tell
Fridgewatch 2100 that the signal it is currently receiving into the P4 analogue input is the value it
should interpret as the maximum load position and display 100 %. An arrow
←
appears to the
right of the value to indicate that the calibration has been fixed.
Check P4 displays 100 % at full load. Unload to minimum and check P4 displays 0 %. Repeat
the calibration procedure if necessary.
Fridgewatch automatically return S36 = 0 when the maximum calibration is fixed.
Fig 33 Calibration of LVDT 4 to 20 mA Signal – HS 3100 New Series, HS 3200 and HS 4200 Series
Compressors