88
CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
Example: Reading a Single Coil
After reviewing the Electrical Schematic for your compressor, you determine that the digital
output for the prelube pump is located on J12-P7,8 (Channel 13). From the table above, the
Absolute Address is decimal 00199 (Relative Address is hexadecimal 00C6) for the output
in question. Therefore, to read the state of the prelube pump output the following command
is issued (the following data are presented in hexadecimal format):
The response from this command is:
The data (01) means that the discrete output is on, or the prelube pump is running.
Absolut
e
Address
(decimal
)
Relative
Address
(hex)
Coil Name - Read Only*
Absolut
e
Address
(decimal
)
Relative
Addres
s
(hex)
Coil Name - Read Only*
00187
00-BA
Digital Output, Channel 1 (J15-P7,8)
00203
00-CA
Compressor State - Waiting
00188
00-BB
Digital Output, Channel 2 (J15-P5,6)
00204
00-CB
Compressor State - Coasting
00189
00-BC
Digital Output, Channel 3 (J15-P3,4)
00205
00-CC
Compressor State - Starting
00190
00-BD
Digital Output, Channel 4 (J15-P1,2)
00206
00-CD
Compressor State - Not Ready
00191
00-BE
Digital Output, Channel 5 (J14-P7,8)
00207
00-CE
Compressor State - Ready
00192
00-BF
Digital Output, Channel 6 (J14-P5,6)
00208
00-CF
Compressor State - Surge Unload
00193
00-C0
Digital Output, Channel 7 (J14-P3,4)
00209
00-D0
Compressor State - Autodual Unload
00194
00-C1
Digital Output, Channel 8 (J14-P1,2)
00210
00-D1
Compressor State - Unloading
00195
00-C2
Digital Output, Channel 9 (J13-P7,8)
00211
00-D2
Compressor State - Unloaded
00196
00-C3
Digital Output, Channel 10 (J13-P5,6)
00212
00-D3
Compressor State - Min load
00197
00-C4
Digital Output, Channel 11 (J13-P3,4)
00213
00-D4
Compressor State - Max load
00198
00-C5
Digital Output, Channel 12 (J13-P1,2)
00214
00-D5
Compressor State - Loading
00199
00-C6
Digital Output, Channel 13 (J12-P7,8)
00215
00-D6
Compressor State - Loaded
00200
00-C7
Digital Output, Channel 14 (J12-P5,6)
00216
00-D7
Compressor State - Full Load
00201
00-C8
Digital Output, Channel 15 (J12-P3,4)
00217
00-D8
Compressor State - Analog Input
Failed
00202
00-C9
Digital Output, Channel 16 (J12-P1,2)
00218
00-D9
Any Compressor Trip
00219
00-DA
Any Compressor Alarm
NOTE
: (J15-P7,8) is interpreted as Connector J15, Pins 7 and 8 on the Base Control Module.
* IMPORTANT
:
These coils are
defined as read only. If you decide to write to these coils, unexpected results could occur.
Number of
Device
Function
Address
Coils
CRC
Address
Code
Hi
Lo
Hi
Lo
Lo
Hi
01
01
00
C6
00
01
1D
F7
Device
Function
Byte
CRC
Address
Code
Count
Data
Lo
Hi
01
01
01
01
90
48