60
CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
Pressure Monitoring System (PMS)
Description:
A Pressure Transducer (PT) is used to convert pressure (psi) to a 4-20 mA signal for
monitoring by the CMC.
Component specification:
•
0-50 PSIG (344.75 kPa) range
•
0-200 PSIG (1379 kPa) range
•
Power = 24 VDC
Troubleshooting:
The following table identifies typical problems, probable causes, and appropriate procedures
for verifying the probable cause:
Typical Problem
Probable Cause
Troubleshooting Procedure
Zero OUI readout
Open circuit/cable
disconnected
PMS #1, 2
Loss of power to transmitter
PMS #1
Malfunctioning transmitter
PMS #3, 4
Erratic OUI readout
Loose wire/terminal/connector
PMS #1,2
Incorrect OUI readout
Any
PMS #1, 2, 3, 4