Checking for Power to the Pressure Transmitter
PMS #1
1. Ensure control power is off. Disconnect the wires at the suspect PT and connect a
voltmeter to these wires.
2. With control power on, there should be approximately 24 VDC present at the terminals.
3. If approximately 24 VDC is not present, see the section titled “Control Power System”.
J2
-Floating Analog Inputs, (4-20mA) Channels 1-2
J1-
Grounded Analog Inputs,
(4-20mA) Channels 3-23
Pin 1
Pin 25
BCM
SPAN
®
INGERSOLL RAND
VDC
mA
VAC
Ω
mA COM V
X X X X X
X X X X X
X X X X X
X X X X X
X X X X X
X X X X X
Ω