CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
35
Indicator, Switch and Light Layout
In addition to the CMC OUI there may be a variety of indicators, switches, and lights
mounted on the control panel door. In conjunction with the CMC OUI these devices make up
the User Interface for the CMC. A typical device layout consists of the following lights, push
buttons, and selector switches.
Lights
The lights provided are the green CONTROL POWER ON light, which is integral to the
CONTROL POWER OFF/ON switch, the amber PRELUBE PUMP RUNNING light and the
red TROUBLE INDICATION light.
Push Buttons
The red EMERGENCY STOP push button stops the compressor any time that it is pressed.
This push button is used to initiate a stop in the case of an emergency.
Switches
The CONTROL POWER OFF/ON selector switch turns the panel power on or off
CMC Tuning Procedures
When commissioning a new compressor, troubleshooting an existing compressor, or tuning
a system, the following procedures may be required. The procedures are performed, and
any changes required are made through the CMC OUI. For instructions on how to use the
OUI refer to the section titled User Interface. The following figure will be referenced in the
procedures.
Compressor
Motor
Starter
CT
Bypass
Valve
Inlet
Valve
Check
Valve
Base
Control
Module
PT
1
4-20 mA
4-20 mA
PT
2
Pneumatic Tubing
Plant Air System
Inlet Filter
Block
Valve
Figure 11: Plant Air System