CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
137
SW-2, SW-3, SW-4 (Node Address)
These three switch assemblies are used to set the network node number of the 1770-KF2
module. Set both switches in SW-2 OFF for DH+ link because the node number should be
a 2-digit octal number that identifies the 1770-KF2 as a unique node on DH+. Valid node
numbers for 1770-KF2 in DH+ network are 00 to 77 octal.
First digit (SW-2) should always be set to zero.
SW-2 Setting
1
2
Digit
OFF
OFF
0
OFF
ON
1
ON
OFF
2
ON
ON
3
Second and third digits:
SW-3, SW-4 Setting
1
2
3
Digit
OFF
OFF
OFF
0
OFF
OFF
ON
1
OFF
ON
OFF
2
OFF
ON
ON
3
ON
OFF
OFF
4
ON
OFF
ON
5
ON
ON
OFF
6
ON
ON
ON
7
SW-5 (Network Link Communication Rate)
Switch assembly SW-5 lets you select the communication rate for the 1770-KF2 module’s
network link (DH+). Set both switches ON for a network communication rate of 57,600 bits
per second. Be sure to set all modules on the same DH+ network for this communication
rate.
SW-6 (Asynchronous Link Communication Rate and Diagnostic Commands)
Switches #1, #2, #3 of SW-6 let you select the communication rate for the 1770-KF2
module’s asynchronous port. Meanwhile, switch #4 determines how 1770-KF2 module
treats diagnostic commands sent by a remote DH+ node. It is recommended to set at 9600
baud or higher, and execute received diagnostic commands.
SW-6 Setting
4
Execute received diagnostic commands
ON
Pass any received diagnostic commands to the attached asynchronous
device
OFF
The available baud rate settings are shown below:
Baud Rate
SW-6 Setting
(Bits per second)
1
2
3
110
OFF
OFF
OFF
300
ON
OFF
OFF
600
OFF
ON
OFF