CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
151
Connector Description
Tag
Type
Module Connector
Mating Connector
J1
Microcontroller/Network
(RS422/485) Port
Phoenix MSTBA2,
5/8-G-5, 08
Phoenix MSTBW2,
5/24-ST-5, 08
J2
Service/Modem (RS232)
Port
9 Position “D” Sub
Miniature (Female)
9 Position “D” Sub
Miniature (Male)
J3
Input Power
Phoenix MSTBA2,
5/2-G-5, 08
Phoenix MSTW2,
5/2-ST-5, 08
NOTES:
1. UCM Weight: 410 g [0.90 lb.]
2. UCM Size: Length=136 mm [5.4 in] x Width=143 mm [5.6 in] x Depth=31 mm [1.2 in]
3. All Phoenix connectors may be replaced with an equal supplier.
Connector Input and Output (I/O)
Pin
J1-Microcontroller/Network
Port
Pin
J2-Service/Modem Port
Pin
J3-Input Power
1
IRBUS RS485 Da (DL+)
1
No Connection
1
+12 To +24 VDC (VPOWER)
2
IRBUS RS485 Datalink - (DL-)
2
Transmit (TX)
2
Ground (GND)
3
Ground (GND)
3
Receive (RX)
4
RS422/485 Tr (TX+)
4
No Connection
5
RS422/485 Transmit - (TX-)
5
Signal Common
6
RS422/485 R (RX+)
6
No Connection
7
RS422/485 Receive - (RX-)
7
No Connection
8
Ground (GND)
8
No Connection
9
No Connection
Setting UCM Switches
The UCM has two sixteen position selector switches, A0 and A1.
Switch A0 is used for setting the IRBUS Address for the UCM. This switch can be in any of
the sixteen positions. If there are multiple UCM’s on a single Base Control Module, then each
address for each UCM must be unique. This applies only to multiple UCM’s on a single Base
Control Module.
Switch A1 is unused at this time and must be set to zero.
UCM Port Activity LEDs
The UCM has three light emitting diodes (LEDs) to indicate the activity of the RS232,
RS422/485 and the IRBUS RS485 ports. The following table indicates the different states of
these ports.