Check the Vibration Probe, and Cable
VMS
#3
1. Turn control power off and disconnect the
probe extension cable from the
transmitter.
2. Check resistance of the extension cable
and probe together, the reading should be
7 to 20 ohms.
Probe cable
VDC
mA
VAC
Ω
mA COM V
X X X X X
X X X X X
X X X X X
X X X X X
X X X X X
X X X X X
Ω
Probe extension
cable
Vibration probe
Compressor
casing
Connect test lead
to inner pin.
Connect test lead
to outer shell.
Probe connector
Checking the Vibration Probe
VMS #4
1. Turn control power off and disconnect the
probe extension cable from the
transmitter.
2. Check resistance of the probe alone, the
reading should be 7 to 12 ohms.
VDC
mA
VAC
Ω
mA COM V
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
Ω
Connect test lead
to outer shell.
Connect test lead
to inner pin.
Vibration probe
Probe cable
Probe connector