142
CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
Status
Code
Definition
Comments
11h
Task Overrun
System processing capabilities do not meet requirements for operation. Cycling the
power on the module will restart the system. Once restarted, the program will
operate properly until the same condition reoccurs.
12h
Watchdog Failure
The internal backup system monitor is not operational. BCM hardware should be
replaced. Cycling the power on the module will restart the system. Once restarted,
the program will operate properly until the same condition reoccurs.
13h
Intermodule Data Error
An error has occurred while generating a message to be sent from one BCM to the
other BCM in a multi-module configuration. The module must be reprogrammed.
14h
Calculation Block Error
A stack underflow or overflow has occurred in a calculation block. The module
must be reprogrammed.
15h
Interpolation System Error
An error has occurred in the interpolation block. The module must be
reprogrammed.
16h
Calibration System Error
Occurs during initialization of the EEPROM block. The module must be
reprogrammed.