CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
25
1/4
SETTINGS
INFO
SYSTEM
Motor
Current
System
Pressure
Pressure
Setpoint
105.1
105.0
323.4
Loaded
Inlet
Valve
Bypass
Valve
100
0
Remote
Load Selected
31-AUG-1999 12:00:00
Running Hours: 11445
System Folder – Page 1: System Pressure
2/4
SETTINGS
INFO
SYSTEM
Press Temp Vib
Loaded
Remote
Load Selected
Stage 1 30.1 95.8 0.25
Stage 2 106.6 93.5 0.22
Oil 20.3 105.5
3/4
SETTINGS
INFO
SYSTEM
Digital Inputs
Loaded
Remote
Load Selected
Starter Feedback
E-Stop Pressed
Low Seal Air
System Folder - Pages 2,3: Analog/Digital Inputs
SYSTEM Folder
The SYSTEM folder provides information about the compressor system. The number of
pages in this folder is at least four; but could be more for two stage machines with special
analog options purchased, or for
compressors with three stages or
more.
This page shows the main
compressor operating parameters,
running hours, date and time. The
System Pressure and Pressure
Setpoint are in units as defined by
the Settings page, Motor Current is
in Amps and valve positions are in
percent open. Pressure Setpoint is
always editable while the Inlet and
Bypass Valve positions are edit
enabled when in the Manual mode only. These are the only editable settings in any folder
other than the Settings Folder.
Info Folder Page 1 Edit Parameters Table
Variable
Units
Minimum
Value
Maximu
m
Value
Step
Size
Pressure Setpoint
pressure
0.0
999.9
0.1
Inlet Valve Position (
manual mode only
)
percent
0
100
1
Bypass Valve Position (
manual mode only
)
percent
0
100
1
The Analog Input page provides the
actual value for each stage pressure,
temperature and vibration, oil pressure
and temperature. If additional analog
inputs have been purchased or more
stages exist as standard, it is likely that
an additional page or pages will be
added. The units are as defined by the
Settings page. There are no
changeable setpoints on this page.
The Digital Input page shows the
current state of the digital (discrete)
inputs for the system. The number of
inputs will vary depending upon the
number of optional inputs purchased. A
check in the box to the left of the text
indicates a TRUE condition, whereas,
no check indicates a FALSE condition.
For example, a check mark in the “E-
Stop Pressed” boxed means that the
Emergency Stop push button has been