CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
65
Checking proper operation of the digital devices
DIS #1
1. Verify approximately 24 VDC is present as described in the section titled
“Troubleshooting the Power System”.
2. If approximately 24 VDC is present, install a multimeter with VDC selected between J4 or
J5 pin1 and the input pin (the input pin can be determined from the electrical schematic,
or wire number).
3. Ensure the digital device is not in the trip condition, the meter should read 0 VDC.
4. Actuate the switch, the meter should read approximately 24 VDC.
J3
-Analog Outputs
(4-20mA)
Channels 1-4
Pin 1
Pin 1
J4
-Digital (Discrete)
Inputs (24 VDC),
Channels 1-8
J5
-Digital (Discrete)
Inputs (24 VDC),
Channels 9-16
J6
-RS232 Serial
Data Link (Display),
Female DB9
BCM
VDC
mA
VAC
Ω
mA COM
V
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
Ω
Seal Air Switch