CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
33
5/6
SYSTEM
SETTINGS
INFO
Loaded
Remote
Load Selected
Starting Timer, seconds 20
CT Ratio 60
Motor Failure Trip Enable
Coasting Timer, seconds 240
Setpoint Ramp Rate, pressure/scan 5.0
Inlet Valve Unload Position, % 15
Settings Folder - Page 5: Miscellaneous
6/6
SYSTEM
SETTINGS
INFO
Loaded
Remote
Load Selected
Alarm Trip
Stage 1 Temperature 120 125
Stage 1 Vibration 0.80 1.00
Stage 2 Temperature 120 125
Stage 2 Vibration 0.75 0.95
Oil Pressure 18 16
High Oil Temperature 120 125
Low Oil Temperature 100 95
Settings Folder - Page 6: Alarm and Trip
Coasting Timer is the length of time that it takes for the driver to stop rotating.
CT Ratio is the ratio of the current
transformer primary to the
secondary; i.e., if the CT primary
winding is 300 and the secondary
winding is 5, then the CT Ratio is
60.
When checked, Motor Failure Trip
Enable tests that the zero amp
motor current has been reached
after a start command has been
initiated and that motor current is
not lost while the compressor is
running. Uncheck this box for dry
run conditions.
The Inlet Unload Position is the position of the inlet valve when in the unload state.
Setpoint Ramp Rate is used to prevent system pressure overshoot during compressor
loading.
Additional settings will be added to this page for “special” features.
Settings Folder Page 5 Edit Parameters Table
Variable
Units
Minimum
Value
Maximu
m
Value
Step
Size
Starting Timer
seconds
5
60
1
Coasting Timer
seconds
0
9999
1
CT Ratio
dimensionless
60
9999
1
Inlet Valve Unload Position
percent
0
100
1
Setpoint Ramp Rate
pressure/scan
0
999.9
0.1
WARNING
Failure to set the Coast Timer for a period greater than or equal to the actual
coasting time can result in compressor damage.
The Alarm and Trip Settings Page
provides the means for changing
the analog health monitoring
values. The number of inputs
varies depending upon the number
of compression stages and
optional inputs. Additional pages
will be added as needed after this