CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
7
Service Tool Variable
Names
The following variable names are used in the
CMC Service Tool.
Ad_unload_tmr —
Autodual unload timer. The time delay, in
seconds, at which the machine will be unloaded after the
bypass valve has passed and stayed below the unload point
when Autodual is active.
ASF —
Adjusted Service Factor. The Ingersoll-Rand supplied
value for determining MaxLoad.
Auto_Start_Pressure —
The system pressure, in pressure
setpoint units, at which the machine will start when either
auto hot or cold start is active.
Bat_Var_1 —
Battery Backed Variable 1. Password
character 1 that is entered by the user to enable set point
changes. This value is compared to the system password
character 1.
Bat_Var_2 —
Battery Backed Variable 2. Password
character 1 that is entered by the user to enable set point
changes. This value is compared to the system password
character 2.
Bat_Var_3 —
Battery Backed Variable 3. Password
character 1 that is entered by the user to enable set point
changes. This value is compared to the system password
character 3.
Bat_Var_4 —
Battery Backed Variable 4. Password
character 1 that is entered by the user to enable set point
changes. This value is compared to the system password
character 4.
Bat_Var_5 —
Battery Backed Variable 5. The power on hour
meter.
Bat_Var_6 —
Battery Backed Variable 6. The running hours
hour meter.
Bat_Var_7 —
Battery Backed Variable 7. The loaded hour
meter.
Bat_Var_8 —
Battery Backed Variable 8. The number of
starts counter.
Bv_Closed_Value —
Bypass Valve Closed Value. This
setting determines the value at which the bypass valve is
considered closed. This value is used in logic to determine
when to release the inlet valve from MinLoad control and
enable the inlet valve for pressure control etc.
Bv_Open_Value —
Bypass Valve Open Value. This setting
determines the value at which the bypass valve is considered
open. This value is used in logic to determine when to release
the inlet valve for unloading.
BV_P_PID_D —
Bypass Valve Pressure PID Derivative. The
Bypass valve pressure control derivative constant,
dimensionless.
BV_P_PID_I —
Bypass Valve Pressure PID Integral. The
Bypass valve pressure control integral constant,
dimensionless.
BV_P_PID_P —
Bypass Valve Pressure PID Proportional.
The Bypass valve pressure control proportional constant,
dimensionless.
BV_Unload_Rate —
Bypass Valve Unload Rate. This
setting determines the rate at which the bypass valve will
open during an unload sequence.
Bypass_Valve_C —
Bypass Valve Command. The
position, in percent open, sent to the bypass valve by the
controller. This is the value of an analog output.
Bypass_Valve_Manl —
Bypass Valve Manual. The
manual bypass valve position, in percent open.
Coast_Timer —
The time interval, in seconds, between a
compressor stop or trip and the motor coming to a complete
stop. The timer is used to inhibit restarting.
CT_Ratio —
Current Transformer Ratio. The current
transformer ratio used in displaying the motor current; e.g.
600:5 = 120.
Current_Rate_SP —
The current rate set point for the
analog surge sensor.
HLL —
High Load Limit. The load that the controller
maintains when at MaxLoad.
Inlet_Valve_C —
Inlet Valve Command. The position, in
percent open, sent to the inlet valve by the controller. This
is the value of an analog output.
Inlet_Valve_Manl —
Inlet Valve Manual. The manual inlet
valve position, in percent open.
IV_HLL_PID_D —
Inlet Valve High Load Limit PID Derivative.
The inlet valve MaxLoad control derivative constant,
dimensionless.
IV_HLL_PID_I —
Inlet Valve High Load Limit PID Integral.
The inlet valve MaxLoad control integral constant,
dimensionless.
IV_HLL_PID_P —
Inlet Valve High Load Limit PID
Proportional. The inlet valve MaxLoad control proportional
constant, dimensionless.
IV_P_PID_D —
Inlet Valve Pressure PID Derivative. The
inlet valve pressure control derivative constant,
dimensionless.
IV_P_PID_I —
Inlet Valve Pressure PID Integral. The inlet
valve pressure control integral constant, dimensionless.
IV_P_PID_P —
Inlet Valve Pressure PID Proportional. The
inlet valve pressure control proportional constant,
dimensionless.
IV_TL_PID_D —
Inlet Valve Throttle Limit PID Derivative.
The inlet valve MinLoad control derivative constant,
dimensionless.
IV_TL_PID_I —
Inlet Valve Throttle Limit PID Integral. The
inlet valve MinLoad control integral constant, dimensionless.