CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
131
10
02
0B
0D
4F
00
E1
41
28
10
10
10
03
3F
Please refer to the
PLC5 Typed Read
command section for the method to interpret the 16-
bit discrete values.
Command 0F/Function AA - SLC Typed Logical Write
The CMC is treated as a SLC5/04 when this command is issued. This command writes a
block of data to CMC starting at a specified data table address. You can write to a setpoint
with either an integer or floating point number.
Example: Presetting Analog Setpoint for 32-bit Value
To write 105.4 PSIG as a floating point number to the user pressure setpoint (CMC data
table address, 86h), issue the following command:
DLE
STX
DST
SRC CMD STS
TNS
FNC
Byte
Size
File
No.
File
Type
Ele
No.
S/Ele
No.
Data
DLE
ETX BCC
10
02
0D
0B
0F
00
E1
70
AA
04
0B
8A
86
00
CD
CC
D2
42
10
03
12
The response from this command is:
DLE
STX
DST
SRC
CMD
STS
TNS
DLE
ETX
BCC
10
02
0B
0D
4F
00
E1
70
10
03
48
Example: Presetting a 16-bit Integer and 16-bit Fraction Analog Setpoint
To change the integer and fraction value for the user pressure setpoint to 105.4 PSIG, issue
the command below. The integer portion of the number 105 (00-69h) and the fraction 0.4 is
converted to 4000 (0F-A0h). These four bytes are placed in field B in the order of (69-00-A0-
0Fh).
DLE
STX
DST
SRC CMD STS
TNS
FNC
Byte
Size
File
No.
File
Type
Ele
No.
S/Ele
No.
Data
DLE
ETX BCC
10
02
0D
0B
0F
00
E1
82
AA
04
0B
89
86
00
69
00
A0
0F
10
03
96
The response from this command is:
DLE
STX
DST
SRC
CMD
STS
TNS
DLE
ETX
BCC
10
02
0B
0D
4F
00
E1
82
10
03
36
Example: Forcing a Coil
Forces a single coil to either ON or OFF. Refer to the CMC data table for each coil
supported by the UCM-DF1 interface. See the same example in the
PLC5 Typed Write
command section for more details.
To remotely acknowledge the compressor’s alarm or trip condition, the following command
is issued:
DLE
STX
DST
SRC CMD STS
TNS
FNC
Byte
Size
File
No.
File
Type
Ele
No.
S/Ele
No.
Data
DLE
ETX
BCC
10
02
0D
0B
0F
00
E1
A3
AA
04
0B
89
DC
00
01
00
00
00
10
03
36
The response from this command is:
DLE
STX
DST
SRC
CMD
STS
TNS
DLE
ETX
BCC