CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
67
Power Supply:
•
Input power: 85-132 VAC, or 180-264 VAC (auto-selecting input), 2.5A RMS max, 47-63
Hz.
•
Output power: 24 VDC, 4.3 A maximum at 50 °C.
Troubleshooting:
The following table identifies typical problems, probable causes, and appropriate procedures
for verifying the probable cause:
Typical Problem
Probable Cause
Troubleshooting
Procedure
All analog inputs are zero or negative on System Page
No AC power
CPS #1
No DC power
CPS #2
No analog input
power
CPS #5
OUI displays: “
INGERSOLL-RAND
Centrifugal
Compressor Division”
No CPU power
CPS #8
BCM problems
CMCS #3
OUI is black
No AC power
CPS #1
No DC power
CPS #2
No OUI power
CPS #7
Event Log indicates all digital alarms and trips active
No AC power
CPS #1
No DC power
CPS #2
No digital input
power
CPS #3
All digital outputs not working
No AC power
CPS #1
No DC power
CPS #2
No digital output
power
CPS #4
All analog outputs not working
No AC power
CPS #1
No DC power
CPS #2
No analog output
power
CPS #6
No AC power
CPS #1
1. Ensure control power is off.
2. Install a multimeter set for VAC between pins 1 and 3 at connector J1 on the power
supply.
3. Restore control power, the meter should read 120 VAC or 220 VAC depending upon the
rated supply power. The rated supply power can be verified from the electrical
schematic.