68
CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
No DC power
CPS #2
1. Ensure control power is off.
2. Install a multimeter set for VDC between pins 11-14 and 7-10 at connector J2 on the
power supply.
3. Restore control power, the meter should read approximately 24 VDC. If approximately
24 VDC is not present, check F1 on the power supply, if fuse is good, the power supply
may be faulty.
4. Ensure control power is off.
5. Install a multimeter set for VDC between pins 1 and 2 at connector J10 on the BCM.
6. Restore control power, the meter should read approximately 24 VDC. If approximately
24 VDC is not present, check the wiring between the power supply and the BCM.
No digital input power
CPS #3
1. Ensure control power is off.
2. Install a multimeter set for VDC between pin 1 at connector J4 on the BCM and the
ground bar.
3. Restore control power, the meter should read approximately 24 VDC. If approximately
24 VDC is not present, check F103 on the BCM, if F103 is good, check for DC power.
No digital output power
CPS #4
1. Ensure control power is off.
2. Install a multimeter set for VAC between pin 1 at connector J12 on the BCM and the
ground bar.
3. Restore control power, the meter should read 120 VAC or 220 VAC depending upon the
rated supply power. The rated supply power can be verified from the electrical
schematic.
No analog input power
CPS #5
1. Ensure control power is off.
2. Install a multimeter set for VDC between pin 26 at connector J1 on the BCM and the
ground bar.
3. Restore control power, the meter should read approximately 24 VDC. If approximately
24 VDC is not present, check F102 on the BCM, if F102 is good, check for DC power.
No analog output power
CPS #6
1. Ensure control power is off.
2. Install a multimeter set for VDC between pin 2 at connector J3 on the BCM and the
ground bar.
3. Restore control power, the meter should read approximately 24 VDC. If approximately
24 VDC is not present, check F102 on the BCM, if F102 is good, check for DC power.
No OUI power
CPS #7
1. Ensure control power is off.
2. Install a multimeter set for VDC between pins 1 and 2 at connector J1 on the OUI.
3. Restore control power, the meter should read approximately 24 VDC. If approximately
24 VDC is not present, check F101 on the BCM, if F101 is good, check for DC power.