100
CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
CAUTION
For all of the following Remote Coils, the compressor’s REMOTE
COMMUNICATIONS DISABLED/ENABLED selector switch must be in the ENABLED
position for these commands to execute. When DISABLED, the CMC ignores (there is
no exception response) these coils being forced ON or OFF.
Example: Forcing a Coil
For all MODBUS devices, a value of FF 00 hex requests the coil to be ON. A value of 00 00
requests it to be OFF. All other values are illegal and will not affect the coil.
NOTE
: For the
CMC, forcing the above listed coils OFF is not meaningful because the default state of each
of the above coils is OFF. When using these commands, they should be sent once
(momentary) and the CMC will execute the commands. To remotely reset the compressor,
the following command is issued:
The response from this command is identical to the command sent:
Function 06 - Preset Single Register
Presets a value into a single holding register (MODBUS 4x reference). When broadcast, the
function presets the same register reference in all attached slaves. Refer to the table for the
Holding Register list for the MODBUS Absolute Addresses supported by the CMC-MODBUS
Interface.
Absolute
Address
(decimal)
Relative
Address
(hex)
Coil Name - Write Only
00221
00-DC
Remote Horn Silence
(Acknowledge)
00222
00-DD
Remote Reset
00223
00-DE
Remote Load
00224
00-DF
Remote Unload
00225
00-E0
Remote Start
00226
00-E1
Remote Stop
Forced
Device
Function
Address
Data
CRC
Address
Code
Hi
Lo
Hi
Lo
Lo
Hi
01
05
00
DD
FF
00
1C
00
Number of
Device
Function
Address
Registers
CRC
Address
Code
Hi
Lo
Hi
Lo
Lo
Hi
01
05
00
DD
FF
00
1C
00