80
CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
General Sequence of Operation
Starting Methodology
1. The panel power is turned on. The compressor is WAITING.
2. The CMC Panel mounted switch for DRIVER SPEED RATED/IDLE (when supplied for
an electronic governor) should be put into the IDLE position. This switch is wired to a
discrete input (Driver Speed Rated/Idle) in the CMC and is sent on the discrete output
(Driver Speed Rated/Idle) to the governor.
3. When the two-minute waiting timer has expired, the compressor is NOT READY.
Unloaded
Coasting
Starting
Loading
Loaded
MinLoad
Full Load
MaxLoad
Unloading
Unloaded
Power
On
Zero Speed Offset (15 rpm)
Minimum Slow Roll (25%)
Maximum Slow Roll (50%)
Low Alarm (95%)
MaxLoad (HLL)
Low Trip (93%)
Rated "Full Load" (100%)
Overspeed Alarm (105%)
Overspeed Trip (108%)
Mechanical Trip (110%)
(0%)
SPEED
Rotating
Stopped
Compressor Operating States
for Turbine and Diesel Driven Packages
Not Ready
Ready
Waiting
Any
Stops or
Trips
Start
No
Stops or
Trips and
Latch