CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
119
Data
Address
(decimal)
Data
Address
(hex)
Description
Data
Address
(decimal)
Data
Address
(hex)
Description
201
C9
Digital Output, Ch 16 (J12-P1,2)
213
D5
Compressor State - Loading
202
CA
Compressor State - Waiting
214
D6
Compressor State - Loaded
203
CB
Compressor State - Coasting
215
D7
Compressor State - Full Load
204
CC
Compressor State – Starting
216
D8
Compressor State - Analog Input Failed
205
CD
Compressor State - Not Ready
217
D9
Any Compressor Trip
206
CE
Compressor State - Ready
218
DA
Any Compressor Alarm
207
CF
Compressor State - Surge Unload
220
DC
Remote Acknowledge
208
D0
Compressor State - Autodual Unload
221
DD
Remote Reset
209
D1
Compressor State - Unloading
222
DE
Remote Load
210
D2
Compressor State - Unloaded
223
DF
Remote Unload
211
D3
Compressor State - Min load
224
E0
Remote Start
212
D4
Compressor State - Max load
225
E1
Remote Stop
Supported Functions
The listing below shows the DF1 commands supported by the CMC Microcontroller.
Command 0F/Function 68 - PLC5 Typed Read
The CMC is treated as a PLC5 when this command is issued. This command reads a block
of data from CMC starting at a specified data table address.
As to the format of floating point number, Allen-Bradley DF1 protocol always put low byte
first then high byte, low word first then high word, which is different from the UCM-MODBUS
protocol. The byte format for a floating point value, 105.4, is differentiated between the two
interfaces as below (Byte 1 to 4 is in the order of transmission):
Example: Reading an Analog Input
After reviewing the Electrical Schematic for your compressor, you determine that the analog
input for system pressure is located on J1-P1 (Channel 3). From the CMC data table above,
the address is 03h. The UCM should be configured to represent data type as desired.
Following is a table illustrating how the PLC5 system address is mapped to the CMC data
table address.
Command
Code
(hex)
Function
Code
(hex)
Function Name
0F
68
PLC5 Typed Read
0F
67
PLC5 Typed Write
0F
A2
SLC Typed Logical Read
0F
AA
SLC Typed Logical Write
Floating Point Byte Representation
Protocol
Byte 1
Byte 2
Byte 3
Byte 4
UCM-MODBUS
42
D2
CC
CD
UCM-DF1
CD
CC
D2
42