CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
31
3/6
SYSTEM
Loaded
Remote
Load Selected
PB IT D
Pressure 10.0 0.50 0.00
Pressure 10.0 0.50 0.00
MinLoad (TL) 25.00 0.50 0.00
MaxLoad (HLL) 99.99 0.50 0.00
SETTINGS
INFO
Inlet Valve
Bypass Valve
rep/sec sec
Settings Folder - Page 3: Control Parameters (PID
Settings)
CAUTION
The MaxLoad (HLL) value should not exceed the value determined in the
section titled Setting MaxLoad. Failure to set this properly could result in damage to
the motor.
CAUTION
When Surge Indexing is enabled and the compressor surges several times,
the compressor will begin bypassing air sooner than when Surge Indexing is disabled.
You should periodically reset the MinLoad Control Setpoint to prevent excessive air
bypass.
CAUTION
Repeated surging can cause damage to the compressor; therefore, use
caution when desensitizing the Surge Sensitivity setting.
The Control Parameters Page is
used for matching the control
system to the local application.
The Proportional Band (PB),
Integral Time (IT) and Derivative
(D) settings are provided for both
the inlet valve and bypass valves.
This gives the controller precise
control for modeling the air
system over the entire operating
range of the compressor. With
this release, the Derivative
constant has been added to give
even more capability to match the
control system to the air system. However, we recommend that this value remain at zero
unless you have full understanding of how this parameter works.
Settings Folder Page 3 Edit Parameters Table
Variable
Units
Minimum
Value
Maximu
m
Value
Step
Size
Each PB (Proportional Band)
dimensionless
0.0
99.99
0.1