CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
59
Checking proper operation of the I/P and positioner
VCS #2
1. Connect a 4-20 mA simulator to the I/P.
2. Ensure instrument air is present at the supply connection on the I/P.
3. Vary the simulator between 4-20 mA. The output of the I/P and the positioner should
follow. If the valve tracks the 4-20 mA signal correctly the I/P and the positioner are
satisfactory.
INGERSOLL-RAND
Centrifugal Compressor Division
Highway 45 South
Mayfield, KY. 42066
Parts Service (800) 247-8640
mA OUT
2 WIRE
OFF
100%
00.0%
DIAL
B A T T E R Y
CHECK
LOOP
ON
XXXXXX
MODEL CL-XXX
00.0% - 100%
5
5
5
4-20 mA SURCE OR
2 WIRE SIMULATOR