66
CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
Control Power System (CPS)
Description:
The control power system provides 24 VDC to the CMC system for processing logic,
displaying data, and monitoring instrumentation. The 24 VDC power supply feeds the Base
Control Module (BCM) at connector J10. Overcurrent protection and power distribution are
performed as shown below:
F100
F101
F102
F103
All BCM Fuses are 5x20mm,
GMA 1.5 amp, Fast Blow
Fuse 5A/250VAC, normal blo.
Power Supply
BCM
J2
+24 VDC pins 11 thru 14
Return pins 7 thru 10
J1
AC1 pin 1
AC2 pin 3
J12-Digital Output Power 120 or 220 VAC (Pin 1)
J10-Power Input (24 VDC)
J9-Current Transformer
(0-5 amp)
J4 & J5 - Digital Input Power 24 VDC (pin 1)
J3- Analog Output Power 24 VDC (pins 2 & 8)
J1- Analog Input Power 24 VDC (pin 26)
Digital Input Power
Analog Input/Output Power
CPU Power
F1
LEGEND:
Wire
Trace
To OUI J2 pin 2
To OUI J2 pin 1
To Ground Bar
BCM shown
cover removed
OUI Power