136
CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
1770-KF2 Setup
A 1770-KF2 module links asynchronous devices (RS-422A or RS-232C) to an Allen-Bradley
Data Highway or Data Highway Plus network. The 1770-KF2 module has 8 switch
assemblies that let you select various communication options. The switch assemblies are
shown in the diagram below:
Switch Assembly
Communication Option
SW-1
Asynchronous link features
SW-2, SW-3, SW-4
Node number
SW-5
Network link communication rate
SW-6
Asynchronous link communication rate
SW-7
DH/DH+ network link section
SW-8
RS-232C/RS-422A selection
CAUTION
The 1770-KF2 module reads the status of these communication option
switches only at power up, so you need to change switch settings with 1770-KF2
powered off.
SW-1 (Asynchronous Link Features)
The following table shows the different combinations available for setting the asynchronous
link with the 5 dipswitches of SW-1.
SW-1 Settings
Protocol
Error
Check
Parity
Embedded
Response
1
2
3
(Duplicate
Message)
ON: ignore
OFF: accept
4
(Hand
Shake)
5
Full Duplex
BCC
None
No
OFF
OFF
OFF
OFF
OFF
Full Duplex
BCC
Even
No
ON
OFF
OFF
OFF
OFF
Full Duplex
BCC
None
Yes
OFF
ON
OFF
OFF
OFF
Full Duplex
BCC
Even
Yes
ON
ON
OFF
OFF
OFF
Full Duplex
CRC
None
Yes
OFF
ON
OFF
OFF
ON
CAUTION
Only the UCM-DF1 driver supports the full duplex options. Half duplex is not
supported.