152
CMC TECHNICAL REFERENCE MANUAL
1X36003 Version 2.52
1996-1999 Ingersoll-Rand Company
Date of Issue: 18-Oct-1999
UCM Communications Parameters
The UCM has three communication ports, RS232, RS422/485 and IRBUS RS485. Each of
these ports has its own communication parameters that it supports.
UCM Timeout
The UCM has three communication ports, RS232, RS422/485 and IRBUS RS485. Each of
these ports has its own communication parameters that it supports.
RS232
RS422
RS485
IRBUS
RS485
UCM State
off
off
off
No power (24 VDC)
on
off
off
Boot mode, check A1 switch for being non-zero (cycle power
to exit boot mode)
on
on
on
Running, but no communication on any port
on
on
blinking
Multi-module job with inter-module communication
blinking
on
blinking
Service Tool in use
blinking
on
on
Service Tool in use, but no response from BCM … check
connection between BCM and UCM
on
blinking
blinking
MODBUS communication in use
on
blinking
on
RS-422 port in use, but no response from BCM … check
connection between BCM and UCM or Modbus and DF1
address
blinking
blinking
blinking
All blinking together imply a continuous reboot or application
problem
Parameter
Service Tool
RS-232
Modbus/DF1
RS-422/485
IRBUS
RS-485
Distance
50 feet (15.2 meters)
4000 feet (1218.3 Meters)
100 feet (30.4 Meters)
Baud Rate
9600
300, 600, 1200, 2400,
9600, 19200, 38400
9600
Parity
None
None, Even, Odd
None
Data Bits
8
8
8
Stop Bits
1
1, 1.5, 2
1
Configurable
No
Yes*
No
* A certified Ingersoll-Rand Service Representative will provide this configuration.